10.6 Electrical data

10.6.1 Air handling unit
MIN. POWER SUPPLY, ONE-PIECE GOLD UNIT WITH ROTARY (RX),
PLATE (PX) OR COIL (CX) HEAT EXCHANGER.
GOLD 04:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 05, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 05, capacity variant 2:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 AT or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 07, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 10 AT or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 07, capacity variant 2:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 AT or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 08, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 AT or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 08, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 11, capacity variant 1:
1-phase, 3-wire, 230 V -10/+15%, 50 Hz, 16 AT or
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 11, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 12, capacity variant 1 and 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 14, capacity variant 1 and 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 20, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 20, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 AT
GOLD 25, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 10 AT
GOLD 25, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 16 AT
GOLD 30, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
20 AT (RX), 16 AT (PX)
GOLD 30, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 AT
GOLD 35, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 AT
GOLD 35, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
20 AT (RX), 25 AT (CX)
116
www.swegon.com
GOLD 40, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 20 AT
GOLD 40, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
25 AT (RX), 32 AT (CX)
GOLD 50, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
20 AT (RX), 25 AT (CX)
GOLD 50, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 32 AT
GOLD 60, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
32 AT (RX), 40 AT (CX)
GOLD 60, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 50 AT
GOLD 70, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
32 AT (RX), 40 AT (CX)
GOLD 70, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
50 AT (RX), 63 AT (CX)
GOLD 80, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
50 AT (RX), 63 AT (CX)
GOLD 80, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 80 AT
GOLD 100, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz,
50 AT (RX), 63 AT (CX)
GOLD 100, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 80 AT
GOLD 120, capacity variant 1:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 80 AT
GOLD 120, capacity variant 2:
3-phase, 5-wire, 400 V -10/+15%, 50 Hz, 125 AT
We reserve the right to alter specifications without notice.