6.4.11 Heat
6.4.11.1 Status
All the relevant values can be read here. Used for performance
checks.
6.4.11.2 Pre-heat
By preheating the outdoor air, it is possible to prevent moisture
precipitation in the AHU's outdoor air fi lter, to reduce the risk of
frosting in the heat exchanger and to eliminate the risk that pres-
sure sensors and motor control systems are operating in too low
ambient temperature.
See also the Pre-heat function guide for more detailed informa-
tion.
Settings:
Value
Pre-heat
Pre-heat set point
Periodic operation of pump On/Off
Periodic operation of valve
Periodic operation interval
Periodic operation period
Alarm input, function
60
www.swegon.com
Setting
Factory
range
setting
On/Off
Off
-40 – +40°C
5°C
On
On/Off
On
0-168 hrs.
24 hrs.
0-60 min.
3 min.
Inactive/Alarm
Inactive
on open contact/
Alarm on closed
contact/Contactor
function
Heat
Status
Pre-heat