6.4.2.15 Down regulation (airflow/pressure)

Down regulation of the supply air flow is the last step in the
regulation sequence for heating. The supply air fan or both the
supply air and extract air fan can be selected. The extract air fan
only cannot be selected.
See also Section 6.4.2.7.
Down regulation can take place to max. of 50% of the preset
value, however not lower than the min. flow or 20 Pa.
Settings:
Value
Down regulation
We reserve the right to alter specifications without notice.
Setting
Factory
range
setting
Inactive/Supply
Supply air
air/Supply air and
extract air
Down regulation
GB.GOLDSKE.160901
www.swegon.com
49