5.3 Functions

5.3.1 Airfl ow
See also Section 6.4.1 in which the functions for airfl ow
described in detail.
5.3.1.1 Status
All the relevant values can be read here. Used for performance
checks.
5.3.1.2 Operation level
The functions selected (under Installation) and the min. and max.
airfl ows of each AHU size (see the table below) determine which
values can be set.
Values for airfl ow (l/s, m
/s, m
3
or input signal strength (%) can be preset depending on the
function selected.
Low speed
Should always be preset. The value for low speed cannot be
higher than the value for high speed. Low speed can be set to 0,
which means that the AHU is idle.
High Speed
Should always be preset. The value or pressure for high speed
cannot be lower than the value for low speed.
Max. speed
Should always be preset. Used mainly for fi lter calibration. While
fi lter calibration is in progress, the max. speed setting should be
as high as the ventilation system permits without causing any
breakdown. Also used for the pressure regulation, forcing, Heat-
ing Boost and Cooling Boost functions. The value for max speed
cannot be lower than the value for high speed.
Min./Max. fl ows
AIRFLOW
MIN. FLOW FOR
AIRFLOW REG.,
ALL VARIANTS
2
SIZE
m
3
/h
1
m
3
/s
GOLD 04
288
0,08
GOLD 05
288
0,08
GOLD 07
288
0,08
GOLD 08
720
0,20
GOLD 11
720
0,20
GOLD 12
720
0,20
GOLD 14
720
0,20
GOLD 20
1080
0,30
GOLD 25
1080
0,30
GOLD 30
1800
0,50
GOLD 35
1800
0,50
GOLD 40
2700
0,75
GOLD 50
2160
0,6
GOLD 60
3600
1,00
GOLD 70
3600
1,00
GOLD 80
5400
1,50
GOLD 100
5400
1,50
GOLD 120
9000
2,50
1) When adjusting the fl ow, round off the value to the nearest settable step.
2) If pressure regulation is used, the airfl ow can be regulated to zero, however this presupposes a certain static
pressure drop in the ducting (approx. 50 Pa).
3) Cap. variant 1/cap.variant 2
24
www.swegon.com
/h, cfm), pressure (Pa, psi, in.wc)
3
MAX. FLOW, ONE-PIECE
MAX. FLOW,
AHU
ONE-PIECE AHU
ROTARY HEAT EXCH.
PLATE H. EXCH.
(RX)
m
3
/h
m
3
/s
m
1620
0,45
1620
2340
0,65
2340
2700
0,75
2700
3600
1,00
3600
3960
1,10
3960
5040
1,40
5040
5940
1,65
5940
7560
2,10
7560
9000
2,50
9000
11520
3,20
11520
14040
3,90
14040/18000
3,90/5,00
3
3
18000
5,00
23400
6,50
27000
7,50
34200
9,50
39600
11,0
50400
14,0
Airfl ow
Status
Operation level
Air adjustment
Min. /Max. speed
Used for the demand control function (the previous section also
applies to max. speed). Preset the lowest and highest permissible
fl ows for each fan. This means that the fans will not operate
outside these limits, regardless the load.
5.3.1.3 Air adjustment
The speed of the fans can be locked for up to 72 hours. When
the function is activated, the speed is locked at the current speed
of operation. This is practical when making airfl ow adjustments
in the duct system and air terminals. The desired period is preset,
but can be interrupted earlier by selecting Stop or by changing
the time setting to 0.
MAX. FLOW, ONE-PIECE
AHU
COIL H. EXCH. (CX)
(PX)
3
/h
m
3
/s
m
3
/h
0,45
0,65
0,75
1,00
1,10
1,40
1,65
2,10
2,50
3,20
14040
14040/18000
3
18000
23400
27000
34200
39600
50400
We reserve the right to alter specifi cations without notice.
GB.GOLDSKE.160901
MAX. FLOW, SA AND
EA AHU'S (SD)
m
3
/s
m
3
/h
m
3
2160
0,6
2880
0,8
2880
0,8
4320
1,2
4320
1,2
6480
1,8
6480
1,8
10080
2,8
10080
2,8
14400
4,0
3,90
14400
4,0
3,90/5,00
18000/21600
5,0/6,0
3
3
5,00
20160
5,6
6,50
28800
8,0
7,50
28800
8,0
9,50
43200
12,0
11,0
43200
12,0
14,0
64800
18,0
SMALLEST
STEP
/s
m
3
/h
m
3
/s
25
0,01
25
0,01
25
0,01
25
0,01
25
0,01
25
0,01
25
0,01
25
0,01
25
0,01
25
0,01
100
0,05
100
0,05
3
100
0,05
100
0,05
100
0,05
100
0,05
100
0,05
100
0,05