Cooling mode
The mutual order for the cooling mode regulation sequence can
be selected as specified below.
Functions that have not been selected have no effect on the
relevant regulation sequence.
Value
Cooling mode
* 1 = HX - Cooling Boost - Extra regulation sequence - ReCO
Cooling
2 = HX - Cooling Boost - Extra regulation sequence - Cooling -
ReCO
2
3 = HX -Cooling Boost - Cooling - ReCO
Extra regulation sequence
4 = HX - Cooling Boost - Cooling - Extra regulation sequence -
ReCO
2
5 = HX - ReCO
- Cooling Boost - Cooling -
2
Extra regulation sequence
6 = HX - ReCO
- Cooling Boost - Extra regulation sequence -
2
Cooling
HX (heat exchanger):
The temperature efficiency of the air handling unit's heat
exchanger is modulated to provide max. cool recovery.
Cooling Boost (Economy):
Involves increasing the supply air and extract air airflows to
convey more cooling energy to the premises. The flow increase
takes place between the current flow and the preset max. flow.
Extra regulation sequence:
Used in the cooling mode for air cooler (if required), etc.
ReCO
:
2
Recirculated air is variably mixed in up to the lowest permissible
supply airflow. Assumes inclusion of the TCBR air recirculation
section accessory.
Cooling:
Air cooler provides cooling capacity.

6.4.2.9 Min. exhaust air

The min. exhaust air function can be used whenever the
exhaust air temperature is not permitted to be below a
predetermined value.
The function controls the heat exchanger rotor speed (efficiency)
in order to limit the exhaust air temperature to the required
value. The function decelerates the heat exchanger rotor speed
from the current level, until the exhaust air temperature reaches
the preset minimum permissible setting.
Exhaust air regulation requires a separateTBLZ-1-58-aa tempera-
ture sensor (accessory) fitted in the AHU's exhaust air.
See separate installation instructions for the TBLZ-1-58-aa Inter-
nal temperature sensor.
Settings:
Value
Min. exhaust air
Min. exhaust air temperature
44
www.swegon.com
Setting
Factory
range
setting
1/2/3/4/5/6*
1
-
2
Setting
Factory
range
setting
On/Off
Off
-40 – + 20,0 °C
5.0 °C
-
2
Min. exhaust air
We reserve the right to alter specifications without notice.
GB.GOLDSKE.160901