6.4.2.6 Neutral zone

The neutral zone prevents the cooling and heating systems from
counteracting each other.
The preset neutral zone is added to the set point for heating and
the sum of these provides the set point for cooling.
When extract air regulation is active, the supply air set point is
not affected. The neutral zone has no effect if the unit is operat-
ing in the ERS regulation mode.
Settings:
Value
Supply air, temperature control
Extract air, temperature control
6.4.2.7 External temperature sensors
An extract air duct temperature sensor, TBLZ-1-76, can be con-
nected to the air handling unit's control circuit card. See separate
instructions for installation.
Up to four external room temperature and/or outdoor tempera-
ture sensors can be wired to the air handling unit's control circuit
card. The TBLZ-1-24-2 room temperature sensor or TBLZ-1-24-3
outdoor temperature sensor accessories should be used. See
separate installation instructions.
The sensor can be selected to control only intermittent night
heat and/or summer night cooling (the AHU is then controlled
during the daytime in response to signals from the internal
sensor inside the AHU).
Locate the temperature sensors at suitable places to obtain rep-
resentative readings.
The air handling unit is controlled in response to a computed
mean value of the temperature sensors' readings, alternatively in
response to signals from the temperature sensor that measures
the lowest or highest value.
As an alternative, a temperature reading can be transmitted to
the air handling via communication from e.g. a main system.
The same provision is available for room sensors for the Xzone
function.
Settings:
Value
Extract air duct, temperature
sensor
Room sensor 1
Room sensor 2
Room sensor 3
Room sensor 4
Room sensor function
Room temperature from
communication
Room temperature, for
intermittent night heat only
Room temperature, for
summer night cooling only
Outdoor air sensor 1
Outdoor air sensor 2
Outdoor air sensor 3
Outdoor air sensor 4
Outdoor air sensor function
Outdoor temperature from
communication
42
www.swegon.com
Setting
Factory
range
setting
0.0 - 10 K
0.5 K
0.0 - 10 K
0.5 K
Setting
Factory
range
setting
On/Off
Off
On/Off
Off
On/Off
Off
On/Off
Off
On/Off
Off
Medium/min./Max.
Medium
On/Off
Off
On/Off
Off
On/Off
Off
On/Off
Off
On/Off
Off
On/Off
Off
On/Off
Off
Medium/min./Max.
Medium
On/Off
Off
Neutral zone
External temperature
sensors
We reserve the right to alter specifications without notice.