Alarm text
Function
17:4 ROTARY HEAT EXCHANGER, ROTATION DETECTOR TRIPPED
No impulses from the rotation detector are registered with
the heat exchanger controller.
17:5 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER OVER-
CURRENT
Heat exchanger motor controller has registered excessively
high current supplier to the drive motor.
17:6 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER UNDER-
VOLTAGE
Low feed voltage is supplied to the rotary heat exchanger's
motor controller.
17:7 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER OVER-
VOLTAGE
High feed voltage is supplied to the rotary heat exchanger's
motor controller.
17:8 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER EXCESS
TEMPERATURE
High temperature (90°C) inside the heat exchanger's motor
controller.
17:9 ROTARY HEAT EXCHANGER, MOTOR CONTROLLER START
UP ERROR
Drive motor does not rotate during start up.
Alarm group 18: AYC
18:1 AYC, I/O MODULE No. 7 COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct
communication with I/O module No. 7 for AYC.
18:2 AYC HEATING, TEMPERATURE SENSOR DEFECTIVE
Heating temperature sensor is defective or is not connected.
18:3 AYC HEATING, VALVE MONITORING TRIPPED
The heated water valve actuator is defective.
18:4 AYC HEATING, PUMP MONITORING TRIPPED
The heated water pump is defective.
18:5 AYC HEATING, TEMPERATURE BELOW SET POINT LIMIT
Heating water temperature is below preset set point longer
than 30 minutes.
18:6 AYC HEATING, TEMPERATURE ABOVE SET POINT ALARM
LIMIT
5)
Heating water temperature exceeds preset set point longer
than 30 minutes.
18:9 AYC COOLING, TEMPERATURE SENSOR DEFECTIVE
Temperature sensor for the AYC function (All Year Comfort)
cooling is defective or is not connected.
18:10 AYC COOLING, VALVE MONITORING TRIPPED
The chilled water valve actuator is defective.
18:11 AYC COOLING, PUMP MONITORING TRIPPED
The chilled water pump is defective.
18:12 AYC COOLING, TEMPERATURE BELOW SET POINT ALARM
LIMIT
Heating water temperature is below preset set point longer
than 30 minutes.
18:13 AYC COOLING, TEMPERATURE ABOVE SET POINT ALARM
LIMIT
5)
Cooling water temperature exceeds preset set point longer
than 30 minutes.

We reserve the right to alter specifications without notice.

Priority
Stop
0 = Blocked 0 = In operat.
A = A alarm
1 = Stop
B = B alarm
A
1
1)
3)4)
A
1
1)
3)4)
A
1
1)
3)4)
A
1
1)
3)4)
A
1)
1
3)4)
A
1
1)
3)4)
A
0
3)
A
0
3)
B
0
3)
A
0
3)
A
0
3)
B
0
3)
A
0
3)
B
0
3)
A
0
3)
A
0
3)
B
0
3)
GB.GOLDSKE.160901
Delay
Resetting
s = second
0 = manual
m = minute
1 = automatic
h=hour
3 s
0
3 s
0
3 s
0
3 s
0
3 s
0
3 s
0
10 s
1
3 s
1
10 m
0
20 s
0
30 m
0
30 m
0
3 s
1
10 m
0
20 s
0
30 m
0
30 m
0