We Reserve The Right To Alter Specifications Without Notice - Swegon GOLD RX Operation And Maintenance Instructions

Generation e rotary heat exchanger
Hide thumbs Also See for GOLD RX:
Table of Contents

Advertisement

Alarm text
Function
13:9 HUMIDIFIER, ALARM OUTPUT TRIPPED
The humidifier has tripped alarm output.
13:11 VOC SENSOR COMMUNICATION ERROR
The air handling unit's control unit cannot establish correct
communication with the VOC sensor.
13:12 VOC SENSOR, INTERNAL COMMUNICATION ERROR
The air handling unit's control unit cannot achieve correct
communication with the VOC sensor.
13:13 VOC SENSOR, INTERNAL ERROR
VOC sensor defective.
13:14 VOC SENSOR, LEVEL BELOW/ABOVE SET POINT ALARM
LIMIT
The VOC sensor has read a level below or above the set
point alarm limit for more than 60 seconds.
Alarm group 14: Spare
Alarm group 15: Plate heat exchanger
15:1 PLATE HEAT EXCHANGER, I/O-MODULE NO. 2 COMMUNI-
CATION ERROR
The air handling unit's control unit cannot establish cor-
rect communication with I/O module No. 2 for plate heat
exchanger.
15:2 PLATE HEAT EXCHANGER, TEMPERATURE SENSOR NO. 1
DEFECTIVE
Temperature sensor 1 for frost guard in heat exchanger cube
is defective or is not connected.
15:3 PLATE HEAT EXCHANGER, TEMPERATURE SENSOR NO. 2
DEFECTIVE
Temperature sensor 2 for frost guard in heat exchanger cube
is defective or is not connected.
15:4 PLATE HEAT EXCHANGER, DAMPER MONITORING TRIPPED
Damper actuator for plate heat exchanger is defective.
15:7 PLATE HEAT EXCHANGER, I/O-MODULE NO. 3 COMMUNI-
CATION ERROR
The air handling unit's control unit cannot establish correct
communication with I/O module No. 3 for the plate heat
exchanger.
15:8 PLATE HEAT EXCHANGER, BYPASS DAMPER MONITORING
TRIPPED
The bypass damper monitoring function of the plate heat
exchanger has tripped.
15:9 PLATE HEAT EXCHANGER, DAMPER NO. 1 MONITORING
TRIPPED
The section damper 1 monitoring function of the plate heat
exchanger has tripped.
15:10 PLATE HEAT EXCHANGER, DAMPER NO. 2 MONITORING
TRIPPED
The section damper 2 monitoring function of the plate heat
exchanger has tripped.
15:11 PLATE HEAT EXCHANGER, I/O-MODULE NO. 3 COMMUNI-
CATION ERROR
The air handling unit's control unit cannot establish correct
communication with I/O module No. 3 for the plate heat
exchanger.

We reserve the right to alter specifications without notice.

Priority
Stop
0 = Blocked 0 = In operat.
A = A alarm
1 = Stop
B = B alarm
A
0
3)
B
0
3)
B
0
3)
B
0
3)
B
0
3)
A
1
3)4)
A
1
3)4)
A
1
3)4)
A
0
3)4)
A
1
3)4)
A
0
3)4)
A
0
3)4)
A
0
3)4)
A
1
3)4)
GB.GOLDSKE.160901
Delay
Resetting
s = second
0 = manual
m = minute
1 = automatic
h=hour
10 s
0
20 m
1
60 s
1
60 s
1
60 s
1
10 s
1
3 s
1
3 s
1
10 m
0
10 s
1
10 m
0
10 m
0
10 m
0
10 s
1
www.swegon.com
93