This table shows the requirements for protecting the motor insulation and bearings in
drive systems for ABB random-wound motor series (for example, M3AA, M3AP and
M3BP).
Nominal AC sup-
ply voltage
Motor insulation
U n ≤ 500 V
Standard
500 V < U n ≤ 600
Standard
V
or
Reinforced
600 V < U n ≤ 690
Reinforced
V

Additional requirements for non-ABB high-output and IP23 motors

The rated output power of high-output motors is higher than what is stated for the
particular frame size in EN 50347 (2001).
If you plan to use a non-ABB high-output motor or an IP23 motor, consider these
additional requirements for protecting the motor insulation and bearings in drive systems:
If motor power is below 350 kW: Equip the drive and/or motor with the filters and/or
bearings according to the table below.
If motor power is above 350 kW: Consult the motor manufacturer.
Guidelines for planning the electrical installation 93
ABB du/dt and common mode filters, insulated N-end
system
P n < 100 kW
P n < 140 hp
-
+ du/dt
-
+ du/dt
Requirement for
motor bearings
100 kW ≤ P n <
200 kW
140 hp ≤ P n <
268 hp
+ N
+ du/dt + N
+ N
+ du/dt + N
P n ≥ 200 kW
P n ≥ 268 hp
+ N + CMF
+ du/dt + N + CMF
+ N + CMF
+ du/dt + N + CMF