1. The optional EMC C1 filter is selected according to the documentation and installed
as specified in the EMC C1 filter manual. See Main switch and EMC C1 filter options
(+F278, +F316, +E223) installation supplement for ACS580-01, ACH580-01 and
ACQ580-01 frames R1 to R5 (3AXD50000155132 [Multilingual]).
Only available for IP55 (+B056) frames R1...R5, up to 55 kW.
2. The motor and control cables are selected as specified in this manual.
3. The drive is installed according to the instructions given in this manual.
4. The maximum motor cable length with 2 kHz switching frequency is 10 m.
WARNING!
In a domestic environment, this product may cause radio inference, in which case
supplementary mitigation measures may be required.

Category C2

The emission limits are complied with the following provisions:
1. The motor and control cables are selected as specified in this manual.
2. The drive is installed according to the instructions given in this manual.
3. For the maximum motor cable length with 4 kHz switching frequency, see
recommended motor cable length (page
WARNING!
The drive may cause radio interference if used in residential or domestic
environment. The user is required to take measures to prevent interference, in
association to the requirements for the CE compliance listed above, if necessary.
Note: Do not install a drive with the EMC filter connected to a system that the filter is
not suitable for. This can cause danger, or damage the drive.
Note: Do not install the drive with the ground-to-phase varistor connected to a system
that the varistor is not suitable for. If you do, the varistor circuit can be damaged.
If you install the drive to any other system than symmetrically grounded TN-S system,
you may need to disconnect the EMC filter or the ground-to-phase varistor. See sections:
IEC:
Grounding system compatibility check (page 115)
North America:
Grounding system compatibility check (page 166)

Category C3

The drive complies with the standard with the following provisions:
1. The motor and control cables are selected as specified in this manual.
2. The drive is installed according to the instructions given in this manual.
289).