Honeywell UDC3200 Product Manual page 161

Universal digital controller
Hide thumbs Also See for UDC3200:
Table of Contents

Advertisement

Step
Description
2
Select Automatic or
Manual Calibration
3
DO AUTO
Set 0 % value
4
DO AUTO
Set 100 % value
5
DO MAN
Set 0 % value
12/04
Press
Function
Function
Function
or
Function
Function
Function
Function
Function
Function
Function
Function
Function
UDC3200 Universal Digital Controller Product Manual
until you see:
Upper Display = DISABLE
Lower Display = POS PROP
You can calibrate the controller output manually or let the
controller calibrate the output automatically.
If the slidewire has never been calibrated, you must use
DO AUTO first. In the "Automatic Calibration Mode" (DO
AUTO), the controller relays automatically move the motor
in the proper direction.
If desired, however, the motor may be manually positioned
to 0 % and 100 % positions. Disconnect the relay wires.
Use DO MAN. In the "Manual Calibration Mode" (DO
MAN), the motor does not move. Instead, the existing 0 %
and 100 % values may be changed with the
key.
to select automatic or manual calibration.
Upper Display = DO AUTO or DO MAN
Lower Display = POS PROP
If you select...
DO AUTO
DO MAN
ATTENTION
When calibration is terminated, this
selection reverts to DISABL.
The decrement relay is turned on to move the motor to 0 %
position.
Upper Display =
(counts of slidewire feedback 0-3000)
Lower Display = ZERO VAL
When the motor stops, the display should stop counting,
then go to the next step.
The increment relay is turned on to move the motor to
100 % position.
Upper Display =
(counts of slidewire feedback 0-3000)
Lower Display = SPAN VAL
When the motor stops, the display should stop counting,
then, go to Step 8.
You will see:
Upper Display =
(the existing zero calibration value in counts))
Lower Display = ZERO VAL
Output Calibration
Action
or
Then...
go to Step 3
go to Step 5
149