Control; Table 10-16 Set-Up Group - Control - Honeywell UDC3200 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3200:
Table of Contents

Advertisement

10.7.8

Control

Table 10-16 lists all the register addresses and ranges or selections for the function
prompts in Set-up Group Control.
Parameter
Description
PV Source
0085
Tuning
00AC
Parameter
Selection
Automatic
0038
Switchover
Value (used with
172 selection 2
or 3)
Local Setpoint
00AD
Source (Number
of LSPs)
Power Up Mode
0082
Recall
RSP Source
0083
Setpoint
008A
Tracking
Auto Bias
0089
12/04
Modbus Read, Write and Override Parameters plus Exception Codes
Table 10-16 Set-up Group – Control
Register
Data
Address
Type
Hex
Decimal
133
INT
172
INT
056
FP
173
INT
130
INT
131
INT
138
INT
137
INT
UDC3200 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0 = Input 1
1 = Input 2
2 = Input Algorithm 1
R/W
0 = One set only
1 = 2 sets keyboard selected
2 = 2 sets with PV automatic
switchover
3 = 2 sets with setpoint (SP)
automatic switchover
R/W
Within the PV Range in
engineering units
R/W
0 = One Local Setpoint
1 = Two Local Setpoints
2 = Three Local Setpoints
R/W
Control
Mode
0 = MAN
1 = AUTO
2 = AUTO
3 = LAST
4 = LAST
R/W
0 = None
1 = Input 2
R/W
0 = None
1 = LSP = PV (when in
Manual)
2 = LSP = RSP (when
switched)
R/W
0 = Disable
1 = Enable
Setpoint
Mode
LSP
LSP
Last RSP
Last SP
Last Local SP
209