Honeywell UDC3200 Product Manual page 222

Universal digital controller
Hide thumbs Also See for UDC3200:
Table of Contents

Advertisement

Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Control Setpoint
0007
High Limit
Control Setpoint
0008
Low Limit
Control Output
0087
Direction
Output Rate
009C
Enable
Output Rate Up
006E
Output Rate
006F
Down
High Output
000E
Limit
Low Output
000F
Limit
High Integral
0010
Limit
Low Integral
0011
Limit
Output Deadband
004C
for Time Duplex
Output Deadband
0014
for TPSC
Output Drop Off
0014
Limit
Output
0013
Hysteresis
Failsafe Mode
00D5
Failsafe Output
0028
Level
TPSC Power
00B7
Output
210
Register
Data
Address
Type
Hex
Decimal
007
FP
008
FP
135
INT
156
INT
110
FP
111
FP
014
FP
015
FP
016
FP
017
FP
018
FP
020
FP
020
FP
019
FP
213
INT
040
FP
183
INT
UDC3200 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0 to 100% of PV
(engineering units)
R/W
0 to 100% of PV
(engineering units)
R/W
0 = Direct
1 = Reverse
R/W
0 = Disable
1 = Enable
R/W
0.00 to 9999% per minute
R/W
0.00 to 9999% per minute
R/W
–5 to 105% of output
R/W
–5 to 105% of output
R/W
-5 to 105%
R/W
-5 to 105%
R/W
–5 to +25.0%
R/W
0.5 to 5.0%
R/W
-5 to 105%
R/W
0.0 to 100.0% of PV
R/W
0 = Latching
1 = Non latching
R/W
0 to 100%
R/W
0 = Last
1 = Failsafe
12/04

Advertisement

Table of Contents
loading