Configuration
Function Prompt
Lower Display
A1S1TYPE
88
Selections or
Range of Setting
Upper Display
NONE
INPUT 1
INPUT 2
PV
DEV
OUTPUT
SHED
EV ON
EV OFF
MANUAL
REM SP
F SAFE
PV RATE
DIG INP 1
DIG INP 2
DEV 2
BREAK
TCWARN
TCFAIL
PVHOLD
UDC3200 Universal Digital Controller Product Manual
Parameter
Definition
ALARM 1 SETPOINT 1 TYPE—Select what you
want Setpoint 1 of Alarm 1 to represent. It can
represent the Process Variable, Deviation, Input 1,
Input 2, Output, and if you have a model with
communications, you can configure the controller to
alarm on SHED. If you have setpoint programming,
you can alarm when a segment goes ON or OFF.
NO ALARM
INPUT 1
INPUT 2
PROCESS VARIABLE
DEVIATION
OUTPUT (NOTE 1)
SHED FROM COMMUNICATIONS
EVENT ON (SP PROGRAMMING)
EVENT OFF (SP PROGRAMMING)
ALARM ON MANUAL MODE (NOTE 2)
REMOTE SETPOINT
FAILSAFE
PV RATE OF CHANGE
DIGITAL INPUT 1 ACTUATED (NOTE 7)
DIGITAL INPUT 2 ACTUATED (NOTE 7)
DEVIATION FROM LSP 2 (NOTE 3)
LOOP BREAK (NOTE 4)
THERMOCOUPLE WARNING (NOTE 5)
THERMOCOUPLE FAIL (NOTE 6)
PV HOLD
ATTENTION
NOTE 1. When the controller is configured for Three
Position Step Control, alarms set for Output will not
function.
NOTE 2. Alarm 1 is not available if the Timer is
enabled because Alarm 1 is dedicated to Timer
output.
NOTE 3. This Deviation Alarm is based upon
deviation from the 2nd Local Setpoint or Remote SP
regardless of whichever SP is active.
NOTE 4. Loop Break monitors the control loop to
determine if it is working. When enabled, the control
output is checked against the minimum and
maximum output limit settings. When the output
reaches one of these limits, a timer begins. If the
timer expires and the output has not caused the PV
to move by a pre-determined amount, then the alarm
activates, thus signalling that the loop is broken. The
loop break timer value must be configured by the
operator as the AxSx VAL entry. This value is in
seconds with a range of 0 to 3600 seconds. A
setting of 0 is equivalent to an instantaneous loop
break when the output reaches one of its limit
12/04