4.5.2 Viewing the operating parameters

Press the
LOWER DISPLAY
4-3. The lower display will show only those parameters and their values that apply to
your specific model.

Table 4-3 Lower Display Key Parameter Prompts

Lower Display
OUT XX.X
SP XXXX
2SP XXXX
3SP XXXX
RSP XXXX
1IN XXXX
2IN XXXX
POS XX
CSP XXXX
DEV XXXX
PIDSET X
ET HR.MN
OTR HR.MN
RAMPXXXM
SPN XXXX
XXRAHR.MN
XXSKHR.MN
RECYC XX
To BEGIN
RERUN
AUX XXXX
BIA XXXX
TUNE OFF
DO FAST
DO SLOW
12/04
key to scroll through the operating parameters listed in Table
OUTPUT—Output value is shown in percent with one decimal point for all output
types except Three Position Step Control (TPSC). For TPSC, when no slidewire is
connected, this display is an estimated motor position and is shown with no decimal
point. For Position Proportional Control, if the slidewire fails, then the instrument
automatically switches over to TPSC and the OUT display changes with it.
LOCAL SETPOINT #1—Also current setpoint when using SP Ramp.
LOCAL SETPOINT #2
LOCAL SETPOINT #3
REMOTE SETPOINT
INPUT 1—Used only with combinational input algorithms.
INPUT 2
SLIDEWIRE POSITION—Used only with TPSC applications that use a slidewire input.
COMPUTER SETPOINT—When SP is in override.
DEVIATION—Maximum negative display is –999.9.
TUNING PARAMETER —where X is either 1 or 2.
ELAPSED TIME—Time that has elapsed on the Timer in Hours.Minutes.
TIME REMAINING—Time remaining on the Timer in Hours.Minutes. The "O" is a
rotating clock face.
SETPOINT RAMP TIME—Time remaining in the Setpoint Ramp in minutes.
SETPOINT NOW—Current Setpoint when SP Rate is enabled. The SP XXXX display
shows the "target" or final setpoint value.
RAMP SEGMENT NUMBER AND TIME REMAINING—Set Point Programming
display. XX is the current segment number and HR.MN is the time remaining for this
segment in Hours.Minutes.
SOAK SEGMENT NUMBER AND TIME REMAINING— Set Point Programming
display. XX is the current segment number and HR.MN is the time remaining for this
segment in Hours.Minutes.
NUMBER OF SP PROGRAM RECYCLES REMAINING
RESET SP PROGRAM TO START OF FIRST SEGMENT
RESET SP PROGRAM TO START OF CURRENT SEGMENT
AUXILIARY OUTPUT—Displayed only when output algorithm is not Current Duplex.
BIAS—Displays the manual reset value for algorithm PD+MR.
LIMIT CYCLE TUNING NOT RUNNING—Appears when Accutune is enabled but not
operating.
Limit Cycle Tuning with the objective of producing quarter-damped tuning parameters.
This tuning may result in PV overshoot of the SP setting.
Limit Cycle Tuning with the objective of producing damped or Dahlin tuning
parameters, depending upon the detected process deadtime. The tuning parameters
calculated by this selection are aimed at reducing PV overshoot of the SP setting.
UDC3200 Universal Digital Controller Product Manual
Monitoring and Operating the Controller
Description
101