Modbus Read, Write and Override Parameters plus Exception Codes

10.7 Configuration Parameters

Overview
Listed on the next pages are the identifying codes for the parameters in the various Set-up
Groups in the UDC3200 Process Controller. Most of the parameters are configurable
through the hosts. Some are Read Only and are indicated as such and cannot be changed.
Reading or Writing
Do a Read or Write, depending on your requirements, using the identifying code and
format code listed in the tables. The range or selection available for each range is listed in
the tables.
10.7.1

Tuning

Table 10-9 lists all the register addresses and ranges or selections for the function
parameters in the Set-up Group Tuning.
Parameter
Description
Hex
Gain #1 or PB
0001
Note 1
Rate #1
0002
Note 1
Reset #1
0003
Note 1
Manual Reset
000D
Gain #2 or PB #2
0004
Note 1
Rate #2
0005
Note 1
Reset #2
0006
Note 1
Cycle Time #1
0015
Cycle Time #2
0016
192
Table 10-9 Set-up Group – Tuning
Register
Data
Address
Type
Decimal
001
FP
002
FP
003
FP
013
FP
004
FP
005
FP
006
FP
21
INT
22
INT
UDC3200 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
R/W
0.01 to 1000 Gain
0.1 to 1000 PB
R/W
0.00 to 10.00
R/W
0.02 to 50.00
R/W
–100 to +100
R/W
0.01 to 1000 Gain
0.1 to 1000 PB
R/W
0.00 to 10.00
R/W
0.02 to 50.00
R/W
1 to 120 seconds
R/W
1 to 120 seconds
12/04