Modbus Read, Write and Override Parameters plus Exception Codes
Parameter
Description
Hex
Digital Input
00BC
#1
Combinations
Digital Input
00BB
#2 *
Digital Input
00BC
#2
Combinations
* Auxiliary Output and Digital Input #2 are mutually exclusive.
214
Register
Data
Address
Type
Decimal
188
INT
187
INT
189
INT
UDC3200 Universal Digital Controller Product Manual
Access
Data Range or
Enumerated Selection
0 = Disable
R/W
1 = +PID2
2 = +Direct
3 = +LSP2
4 = +Disable Accutune
5 = +LSP1
6 = +Run
R/W
Same as Digital Input #1
0 = Disable
R/W
1 = +PID2
2 = +Direct
3 = +LSP2
4 = +Disable Accutune
5 = +LSP1
6 = +Run