Table 6-4 Auxiliary Output Calibration Procedure - Honeywell UDC3200 Product Manual

Universal digital controller
Hide thumbs Also See for UDC3200:
Table of Contents

Advertisement

Procedure
The procedure for calibrating the auxiliary output is listed in Table 6-4.
Make sure "LOCK" in the Tuning Set Up group is set to "NONE" (see Subsection 3.4).
Step
Operation
1
Enter Calibration
Mode
2
Calibrate 0 %
3
Calibrate 100 %
4
Exit the
Calibration Mode
12/04

Table 6-4 Auxiliary Output Calibration Procedure

Press
Upper Display = CALIB
Setup
Setup
Lower Display = AUX OUT
until you see
You will see:
Function
Function
Function
Upper Display = A Value
Lower Display = ZERO VAL
until the desired 0 % output is read on the milliammeter.
or
Normally, this will be the setting that produces 4 mA.
To store the 0 % value you will see:
Function
Function
Function
Upper Display = A Value
Lower Display = SPAN VAL
until the desired 100 % output is read on the milliammeter.
or
Normally, this will be the setting that produces 20 mA.
The controller stores the span value.
Function
Function
Function
To exit the calibration mode.
Lower
Lower
Lower
Display
Display
Display
UDC3200 Universal Digital Controller Product Manual
Output Calibration
Result
147