Contact Closure Input (CCI) Setup (continued)
(wired directly to the GRAFIK Eye
The integral contact closure input (CCI) on the back of the GRAFIK Eye
is compatible with either type of contact closure device:
Maintained (default): The GRAFIK Eye
closure and a contact open/release event.
Example: "CCI Mode" set to "Afterhours." Contact closure starts "Afterhours."
Contact open/release ends "Afterhours."
Momentary: The GRAFIK Eye
Example: "CCI Mode" set to "Afterhours." Contact closure starts "Afterhours."
Contact open/release has no effect. Second contact closure ends "Afterhours."
Changing the type of contact closure input:
1. Enter programming mode.
Main menu
2. Use the Master buttons to highlight "CCI Setup" and press the
Save Mode
"OK" button to accept.
CCI Setup
3. Use the Master buttons to highlight "CCI Type" and press the
"OK" button to accept.
4. Use the Master buttons to highlight the type you wish the CCI
to control. Press the "OK" button to accept.
CCI menu
5. The info screen will confirm that your setting has been saved.
CCI Mode
6. Exit programming mode.
CCI Type
Note: The "Emergency CCI Mode" is different from the other
CCI Type
Maintained
Saved
Saved
®
QS control unit)
®
QS control unit will act on both a contact
®
QS control unit will act on only contact closure events.
®
CCI modes in that "Emergency Mode" will activate on
a contact open/release and will deactivate on a contact
closure. The CCI must be set to "Maintained" (default) for
proper "Emergency Mode" operation.
QS control unit
®
GRAFIK Eye
QS Control Unit Installation and Operation Guide 24
®