Text block
The text block is used to read or write texts via the data
block.
STX
LGE
ADR
PKE
Illustration 7.8

7.3.7 The PKE Field

The PKE field contains two sub-fields: Parameter command
and response AK, and Parameter number PNU:
PKE
IND
AK
PNU
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Illustration 7.9
Parameter commands master ⇒ slave
Bit no.
15
14
13
0
0
0
0
0
0
0
0
1
0
0
1
1
1
0
1
1
1
1
1
1
Table 7.4
Response slave ⇒master
Bit no.
15
14
13
0
0
0
0
0
0
0
0
1
0
1
1
1
1
1
Table 7.5
VLT Automation Low Harmonic Drive Operating Instructions
IND
Ch1
Ch2
PWE
PWE
high
low
Parameter command
12
0
No command
1
Read parameter value
0
Write parameter value in RAM (word)
1
Write parameter value in RAM (double word)
1
Write parameter value in RAM and EEprom (double word)
0
Write parameter value in RAM and EEprom (word)
1
Read/write text
Response
12
0
No response
1
Parameter value transferred (word)
0
Parameter value transferred (double word)
1
Command cannot be performed
1
text transferred
®
MG34O202 - VLT
is a registered Danfoss trademark
Chn
PCD1
Bits no. 12-15 transfer parameter commands from master
to slave and return processed slave responses to the
master.
PCD2
BCC