Extended Parameters; Input/Output Parameters; Low-Speed Signal - Toshiba TOSVERT VF-AS1 Instruction Manual

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

6. Extended parameters

Extended parameters are provided for sophisticated operation, fine adjustment and other special purposes.
⇒ Refer to Section 11, Table of parameters.
6.1

Input/output parameters

6.1.1 Low-speed signal

 : Low-speed signal output frequency
• Function
When the output frequency exceeds the setting of  an ON signal will be generated. This signal can be
used as an electromagnetic brake excitation/release signal.
Through the open collector terminal OUT1 or OUT2 (24Vdc-50mA [max.]).
[Parameter setting]
Title

Output frequency [Hz]
Low-speed signal output
P24-OUT1 terminals (Default setting)
P24-OUT2 terminals
FLA-FLB-FLC terminals
Low-speed signal output: Inverted
[Connection diagram (Sink logic)]
• Output terminal setting
The low-speed signal (ON signal) output function has been assigned to the terminal OUT1 by default. This
setting must be changed to invert the polarity of the signal.
[Parameter setting]
Title

Note: To put out signals to OUT2, select the parameter .
Function
Low-speed signal output frequency
Set frequency

0
Ry
NO
CC
Function
Output terminal function selection
1(OUT1)
Adjustment range
~ Hz
P24
OUT1 (or OUT2)
Adjustment range
~
F-1
E6581528
Default setting

Time [s]
ON
OFF
ON
OFF
Example of setting
(ON signal) or
(OFF signal)
6