Example of wiring of each model
«VFAS1-6110KPC to 6160KPC»
1
«VFAS1-6400KPC to 6630KPC»
Prohibited
Each transformer features one 500V/600V connector and one 690V connector. Connect the connector appropriate
for the line supply (see above). Set the unused connector to the parked position.
500V/50Hz or 600V/60Hz line
Set X2B to X0 (Parked position)
Set X2A to X2 (In-use position)
X2A
X2
VFAS1-6400KPC to 6630KPC drives feature 2 transformers. Make this connection for each transformer.
Unused X0 connectors set to"parke"positon
Transformer connectors
Unused X0 connectors set to "parked" position
Transformer connetors
IMPROPER WIRING PRACTICES
Making a connection in appropriate for the line voltage will damage the transformer(s) and the VFAS1.
Failure to follow this instruction can result in injury and/or equipment damage.
Connection of a transformer
X0
Parked position
X2B
Transformer
In-use position
«VFAS1-6200KPC to 6315KPC»
Grounding
strips
Location of transformers:
VFAS1-6110KPC to 6160KPC
VFAS1-6200KPC to 6315KPC
VFAS1-6400KPC to 6630KPC
Grounding strips
Caution
Set X2A to X0 (Parked position)
Set X2B to X2 (In-use position)
A-16
690V/50Hz line
X0
Parked position
X2A
Transformer
X2B
In-use position
X2