Reset of user-defined parameters (=)
Setting to returns all parameters to the settings saved by setting the parameter =.
* The above settings and allows you to have your own default parameter settings.
Cumulative fan operation time clear (=)
Setting to resets the cumulative fan operation time to the initial value (0 [zero] time). Set this parameter
when replacing the cooling fan, and so on.
Acceleration/deceleration time setting: 0.01 to 600.0 sec. (=)
When is set to , the acceleration/deceleration time can be set within a range of 0.01 to 600.0 sec.
Acceleration/deceleration time setting: 0.1 to 6000 sec. (=)
When is set to , the acceleration/deceleration time can be set within a range of 0.1 to 6000 sec.
500V-50Hz default setting (=)
Setting tocauses default value is to be set for 500V-50Hz.
When to be set after setting default value is to be set for 500V-50Hz (same value as )
Setting tocauses all the following parameters to be changed from factory shipment (setting)
• Base frequency 1
• Base frequency voltage 1
5
. • Upper limit frequency
• VI/II input point 2 frequency
• RR/S4 input point 2 frequency
• Base frequency 2
• Base frequency voltage 2
• Base frequency 3
• Base frequency voltage 3
• Base frequency 4
• Base frequency voltage 4
• RX input point 2 frequency
• AI1 input point 2 frequency
575V-60Hz default setting(=)
Setting tocauses default value is to be set for 575V-60Hz.
When to be set after setting default value is to be set for 575V-60Hz (same value as )
• Base frequency 1
• Base frequency voltage 1
. • Upper limit frequency
• VI/II input point 2 frequency
• RR/S4 input point 2 frequency
• Base frequency 2
• Base frequency voltage 2
• Base frequency 3
• Base frequency voltage 3
• Base frequency 4
• Base frequency voltage 4
• RX input point 2 frequency
• AI1 input point 2 frequency
: 50Hz
• AI2 input point 2 frequency
: 500V
• RP/high-speed pulse input point 2 frequency
: 50Hz
• Automatic light-load high-speed operation frequency : 50Hz
: 50Hz
• Commercial power/inverter switching frequency
: 50Hz
• PID deviation upper limit
: 50Hz
• PID deviation lower limit : 50Hz
: 500V
• Process upper limit
: 50Hz
• PID output upper limit
: 500V
• Forward speed limit input level
: 50Hz
• Reverse speed limit input level
: 500V
• Undervoltage detection level
: 50Hz
• Overvoltage limit operation level
: 50Hz
• Regenerative power ride-through control level : 75%
• Point 2 frequency
: 60Hz
• AI2 input point 2 frequency
: 575V
• RP/high-speed pulse input point 2 frequency
: 60Hz
• Automatic light-load high-speed operation frequency : 60Hz
: 60Hz
• Commercial power/inverter switching frequency
: 60Hz
• PID deviation upper limit
: 60Hz
• PID deviation lower limit : 60Hz
: 575V
• Process upper limit
: 60Hz
• PID output upper limit
: 575V
• Forward speed limit input level
: 60Hz
• Reverse speed limit input level
: 575V
• Undervoltage detection level
: 60Hz
• Overvoltage limit operation level
: 60Hz
• Regenerative power ride-through control level : 75%
• Point 2 frequency
E-44
E6581528
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 50Hz
: 66%
:134%
: 50Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 60Hz
: 66%
:113%
: 60Hz