Guide To Time Of Replacement; Rush Current Suppression Relay Activation Time; Motor Thermal Protection; Braking Resistance Overload Curve - Toshiba TOSVERT VF-AS1 Instruction Manual

High-performance inverter
Hide thumbs Also See for TOSVERT VF-AS1:
Table of Contents

Advertisement

6.33.19 Guide to time of replacement

 : Annual average ambient temperature
• Function
You can set the inverter so that it will calculate the remaining useful life of the cooling fan, main circuit
capacitor and on-board capacitor from the ON time of the inverter, the operating time of the motor, the
output current (load factor) and the setting of  and that it will display and send out an alarm through
output terminals when each component is approaching the end of its useful life.
Title

Note 1: Using , enter the annual average temperature around the inverter. Be careful not to enter the
annual highest temperature.
Note 2: Set  at the time of installation of the inverter, and do not change its setting after the start of use.
Changing the setting may cause a part replacement alarm calculation error.

6.33.20 Rush current suppression relay activation time

 : Rush current suppression relay activation time
6
• Function
This parameter is used to control the rush current suppressing resistor shorting relay when a direct current
is passed or multiple inverters are used with their DC sections connected to each other.
Title

The rush current suppressing relay is activated on the expiration of the time limit set with parameter  after the
voltage in the DC section of the inverter has reached the specified level.
Rush current
suppression relay

6.33.21 Motor thermal protection

 ~  : PTC thermal selection
⇒ For details, refer to Instruction Manual (E6581339) specified in Section 6.42.

6.33.22 Braking resistance overload curve

 : Braking resistance overload time
⇒ Refer to 5.19 for details.
Function
Annual average ambient temperature
Function
Rush current suppression relay
activation time
DC voltage

Adjustment range
: -10~+10°C
: +11~+20°C
: +21~+30°C
: +31~+40°C
: +41~+50°C
: +51~+60°C
Adjustment range
~ sec.
ON
F-62
E6581528
Default setting

Default setting
