1.5.4 Installation

Installation environment

The VF-AS1 Inverter is an electronic control instrument. Take full consideration to installing it in the proper operating
environment.
Prohibited
1
Mandatory
Prohibited
Mandatory
• Operate in areas where ambient temperature ranges from -10°C to 50°C for VFAS1-5015PM to 5075PM , and
from -10°C to 60°C for VFAS1-6022PL to 6630KPC. When the ambient temperature around inverter will rise above
40°C, it will decrease the rating output current. ( depending on the capacity of the inverter used )
Measuring position
Note: The inverter is a heat-emitting body. Make sure to provide proper space and ventilation when installing in
cabinet. When installing inside a cabinet, we recommend the removal of the protective cover.
• Do not place any inflammable substances near the VF-AS1 Inverter.
If an accident occurs in which flames are emitted, this could lead to fire.
• Operate under the environmental conditions prescribed in the instruction manual.
Operation under any other conditions may result in malfunction.
• Do not install the VF-AS1 Inverter in any location subject to large amounts of vibration.
This could cause the unit to fall, resulting in bodily injury.
• Check to make sure that the input power supply voltage is +10%, -15% of the rated supply voltage
written on the rating label (±10% when the load is 100% in continuous operation).
If the input power voltage is not +10%, -15% of the rated power voltage (±10% when the load is
100% in continuous operation) this may result in fire.
Warning
Caution
• Do not install in any location of high temperature, high
humidity, moisture condensation and freezing.
• Avoid locations where there is exposure to water
and/or where there may be large amounts of dust and
metallic fragments.
• Do not install the inverter where there are gases that
corrode metal or solvents that adversely affect plastic.
5cm
5cm
Point of measurement of the
ambient temperature
Point of measurement of the
ambient temperature
A-24