Prohibited
Preventing radio noise
To prevent electrical interference such as radio noise, separately bundle wires to the main circuit's power terminals
(R/L1, S/L2, T/L3) and wires to the motor terminals (U/T1, V/T2, W/T3).
Control and main power supply
The control power supply and the main circuit power supply for the VF-AS1 are the same. If a malfunction or trip
causes the main circuit to be shut off, control power will also be shut off.
If you want to keep the control circuit alive when the main circuit shuts off due to trouble or tripping, you use a
2
transformer (down to 400V) and an optional control power supply backup unit (CPS002Z).
Wiring
• For ground terminal G/E use wires of the size that is equivalent to or larger than those given in table below and
always ground the inverter.
Use as large and short a ground wire as possible and wire it as close as possible to the inverter.
Voltage
class
VFAS1-5015PM
VFAS1-5022PM
VFAS1-5030PM
VFAS1-5040PM
VFAS1-5055PM
VFAS1-5075PM
VFAS1-6022PL
VFAS1-6030PL
VFAS1-6055PL
VFAS1-6075PL
VFAS1-6110PL
VFAS1-6150PL
VFAS1-6185PL
VFAS1-6220PL
VFAS1-6300PL
VFAS1-6370PL
VFAS1-6450PL
VFAS1-6550PL
VFAS1-6750PL
VFAS1-6900PL
VFAS1-6110KPC
VFAS1-6132KPC
VFAS1-6160KPC
VFAS1-6200KPC
VFAS1-6250KPC
VFAS1-6315KPC
VFAS1-6400KPC
VFAS1-6500KPC
VFAS1-6630KPC
Note1: The recommended cable size is that of the cable (e.g. 1500V class cupper cable) with continuous maximum
permissible temperature of 75°C. Ambient temperature is 40°C or less and the wiring distance is 30m or less.
• Do not attach devices with built-in capacitors (such as noise filters or surge absorber) to the output
(motor side) terminal.
This could cause a fire.
Applicable Motor
500V
600V
2HP
1.5kW
2.2kW
3HP
3.0kW
5HP
4kW
7.5HP
5.5kW
10HP
7.5kW
1.5kW
2HP
2.2kW
3HP
4kW
5HP
5.5kW
7.5HP
7.5kW
10HP
11kW
15HP
15kW
20HP
18.5kW
25HP
22kW
30HP
30kW
40HP
37kW
50HP
45kW
60HP
55kW
75HP
75kW
100HP
90kW
125HP
110kW
150HP
132kW
160kW
200HP
185kW
250HP
250kW
350HP
315kW
450HP
400kW
550HP
500kW
700HP
Caution
Grounding wire size
690V
-
2.2kW
3kW
5.5kW
7.5kW
11kW
15kW
18.5kW
22kW
30kW
37kW
45kW
55kW
75kW
90kW
110kW
132kW
160kW
-
200kW
250kW
315kW
400kW
500kW
630kW
B-2
Grounding wire size
(AWG) [Note]
14
14
-
14
14
12
-
-
-
-
-
10
10
10
10
8
8
8
6
6
6
2
-
2
1
2/0
3/0
4/0
4/0
E6581528
2
(mm
) [Note]
2.5
2.5
2.5
2.5
2.5
4
2.5
2.5
2.5
2.5
4
6
10
10
10
16
16
16
25
35
35
50
70
95
150
150
185
150x2
185x2