[Standard connection diagram - sink logic]
The figure below shows an example of typical wiring in the main circuit VFAS1-6110KPC to 6315KPC inverter.
Main circuit power source
500/575V class : 90(125HP)~250kW(350HP)
690V class : 110~315kW
Three-phase 500~690V-50/60Hz
b-contact of
overload relay
*1: AC reactor (PFL): Mandatory for VFAS1-6110KPC and above.
*2: Transformer for fan supply (TRS) ⇒Refer to section 1.4.4.
*3: Every model with a capacity of 160kW or less come with dynamic braking unit drive circuits (GTR7) built into them as
standard equipment, so if your inverter is among these models, connect an external braking resistor (optional) alone.
*4: If you are using a 200kW model or larger, use a braking unit (optional) and an external braking resistor (optional) in
combination.
*5: ⇒ Refer to Section 2.3.2 for switch functions.
*6: The functions assigned to terminals OUT1, VI/II and RR/S4 can be switched by changing parameter settings.
⇒ For details refer to Section 2.3.2.
*7: To supply control power from an external power supply for backing up the control power supplied from the inverter, an
optional control power backup device (CPS002Z) is required. In such a case, the backup device is used at the same time
with the internal power supply of the inverter.
To back up control power, set the parameter  (Control power supply backup option failure monitoring) properly.
⇒ For more information, refer to 6.33.24.
*8: For PWR connection conforming to safety standards, refer to Section 9.3.
*9: TRS(Transformer for fan power supply) can not be used this system for VFAS1-6110KPC and above.
*2
TRS
*2
Transformer for
Fan power Supply
*2
*1
PFL
Transformer
down to 200V
Control power supply
backup (Option) *7
Surge
suppressor
From (a)
*6
(a)
Frequency
Ammeter
meter
Ammeter or voltmeter
B-5
Main
Noise
circuit
filter
Fan
(a)
*7
Control
circuit
*8
*5
*6
*6
(a)
(a)
(a)
External potentiometer
(or voltage signal between RR/S4 and CCA:0~10V)
E6581528
*4
*4
*3
Motor
Forward run signal
Reverse run signal
Reset
Preset speed 1
Preset speed 2
Preset speed 3
Common
Voltage signal:-10~+10V
Voltage signal:0~10V
or current signal:4 (0)~20mA
2