Wiring guide — Wired Indoor Sensors
Use the S1, S2, S3, or S4 terminals for wired sensors.
CAUTION
Electrical Interference (Noise) Hazard.
Can cause erratic system operation.
Keep wiring at least one foot away from large
inductive loads such as motors, line starters,
lighting ballasts and large power distribution
panels.
Use shielded cable to reduce interference when
rerouting is not possible.
IMPORTANT
Erratic temperature readings from a sensor can
occur as a result of any of the wiring practices
described below. Avoid these practices to assure
correct operation. Use shielded cable to reduce
interference if rerouting sensor wiring is not possi-
ble.
— Be sure wires have a cable separate from the ther-
mostat cable.
— Do not route temperature sensor wiring with build-
ing power wiring, next to control contactors or near
light dimming circuits, electric motors or welding
equipment.
— Avoid poor wiring connections.
— Avoid intermittent or missing building earth
ground.
CAUTION
Electrical Shock Hazard.
Can cause electrical shock or equipment
damage.
Disconnect power supply before connecting wiring.
Wiring 4 C7189U1005 sensors (10k ohm) for temperature
averaging network. Select 10K in the Installer Setup (ISU
5030) when using C7189U1005 sensor(s).
EIM
THE NUMBER OF C7189U SENSORS MUST BE
1
A SQUARE NUMBER (1, 4, 9, 16, ETC.)
Fig. 357. Wiring 4 C7189U sensors.
68-0311—07
®
IAQ WITH EIM
1
C7189
C7189
C7189
C7189
M31472
Wiring 2 TR21 sensors (20k ohm) and 1 TR21-A sensor
(10k ohm) for temperature averaging network. Select 20K
in the Installer Setup (ISU 5030) when using 2 TR21
sensors and 1 TR21-A sensor.
EIM
Fig. 358. Wiring 2 TR21 sensors and 1 TR21-A sensor.
Wiring 4 TR21 sensors (20k ohm). Select 20K in the
Installer Setup (ISU 5030) when using TR21 sensor(s).
EIM
Fig. 359. Wiring 4 TR21 sensors.
Wiring 2 TR21-A sensors (10k ohm) for temperature
averaging network. Select 20K in the Installer Setup (ISU
5030) when using 2 TR21-A sensors in series. Note: The
TR21-A sensor must be used in combination with TR21 or
TR21-A sensor.
EIM
Fig. 360. Wiring 2 TR21-A sensors.
158
TR21-A
T3
T4
TR21
TR21
M31473
TR21
TR21
TR21
TR21
M31474
TR21-A
T3
T4
TR21-A
T3
T4
M31475