EX 5/7/11 RT System
4.3
Hot Swapping the Power Module
This operation can be performed without interrupting the load.
Figure 4-1: Disconnecting the power module.
OFF
19
Tower configuration
12
Rack configuration
4 — 4
17
XXX FAULT
1CXXXXXXX
ON
ings
Car d
Sett
10
UPS
100
data
8FF 855E
660 74
IP=
=00 E0D
32
MAC
Res et
RS2
1 2
ET
ON
ERN
ETH
nloa
d
32 Dow
RS2
42
40
7
φ
8
1. Stop the UPS with the OFF button
more than 3 seconds).
Check if UPS is on bypass AC source:
17
LED
is on (If LED
turn the manual bypass and call the after sales
support department).
2. Turn the manual bypass switch
BYPASS position.
3. Switch the battery circuit breaker(s)
OFF position.
CAUTION:
4. Loosen three screws to remove the
Input/Output box.
5. Disconnect the battery cables
from the power module.
The power module can be replaced.
The connected equipment is powered by the
Bypass AC source.
Maintenance
19
17
is not on, do not
7
14
Do not switch the Normal AC
source circuit-breaker
the OFF position. Doing so
will disconnect power to the
load.
40
and
(press
to the
to the
8
to
42
86-86000-00 A01