P042: Jog Frequency; P043: Jog Acceleration Time; P044: Jog Deceleration Time - Panasonic VF100 Instruction Manual

Table of Contents

Advertisement

P042£ºJOG frequency
P043£ºJOG acceleration time
P044£ºJOG deceleration time
Used to set operation frequency, acceleration time and deceleration time during JOG operation.
[Parameter P042: JOG frequency]
Data setting range (Hz)
[Parameter P043: JOG acceleration time]
Data setting range (s)
Setting unit (s)
•EThe display code for 0.04 s. is "0000".
[Parameter P044: JOG deceleration time]
Data setting range (s)
Setting unit (s)
•EThe display code for 0.04 s. is "0000".
Note
•ERun command select should be set to external control. (Value of parameter P003 is "2 to 5".)
•E SW function select should be set to JOG function.
•EWhen SW set to JOG function is turned ON, the JOG operation preparation state is entered.
•EJOG run/stop and forward run/reverse run are applied with terminals No.2 and 3.
•EMeanwhile, refer to function descriptions on page 84.
•EJOG frequency under control of vector is 1Hz to 120Hz.
90
0.5 to 400.0
0.04•E0.1 to 3600
0.1(0.1 to 999.9)¡¢1(1000 to 3600)
0.04•E0.1 to 3600
0.1(0.1 to 999.9)¡¢1(1000 to 3600)