P130: Motor Capacity; P131: No. Of Motor Poles - Panasonic VF100 Instruction Manual

Table of Contents

Advertisement

Note
•E When vector control is selected, output frequency is in the range of 1Hz~120Hz.
•EVector control is valid only when "P128: Carrier frequency" is in the range of 2.5kHz~10.0kH.
When carrier frequency is set to 0.8kHz~1.6kHz and "P129: Vector control select" is set to "1"
(vector control), setting value of carrier frequency will change to 2.5kHz automatically.
P130£ºMotor capacity
Used to set the capacity required to drive the motor when vector control is used.
Note
•E After setting data is changed, data of "P133: Voltage compensation constant" and "P134: Slip
compensation frequency" will automatically change to the motor constant recommended by
our company.
P131£ºNo. of motor poles
Used to set No. of poles required to drive the motor when vector control is used.
Note
•E After setting data is changed, data of "P133: Voltage compensation constant" and "P134: Slip
compensation frequency" will automatically change to motor constant recommended by our
company.
Data setting value
0.4
0.7
1.5
2.2
3.7
Data setting value
No. of motor poles
2
4
6
Motor capacity
0.4kW
0.75kW
1.5kW
2.2kW
3.7kW
2 poles
4 poles
6 poles
P128
Ïà¹Ø
Related
¡«
²ÎÊý
P130
P134
parameters
P129
Ïà¹Ø
Related
¡«
²ÎÊý
P131
P134
parameters
¡«
P129
P130
Ïà¹Ø
Related
¡«
²ÎÊý
P131
P134
parameters