Wiring (Control Circuit); Frequency Setting Potentiometer(Vr) Specifications; Relay Output Contact Specifications; Open Collector Output Specifications - Panasonic VF100 Instruction Manual

Table of Contents

Advertisement

6-2. Wiring (Control circuit)

Wiring(Control Circuit Terminal)
0•` 5V
0•` 10V
4~20mA
0~20mA
Relay output
A
B
C
NO
NC
COM
¡ôFrequency setting potentiometer(VR) specifications: 10 kƒ¶, 1/4W or more
¡ôRelay output contact specifications: 1c no-voltage contact,
230V AC 0.3 A and 30V DC 0.3A (Resistance load)
¡ôOpen collector output specifications: Maximum rating 50V DC£¬50mA
¡¾Wiring Method¡¿
•E For the wiring of the control circuit terminals, use the electric wires after removing
the specific size of wire's insulation.
•E Loosening the terminal screws and insert the wires from under the terminal block,
and tighten the screws to the designated tightening torque.
Note 1) Twist the strands of the uncovered electric wires.
Do not solder them.
Note 2) Tightening loosely causes the wires to be come away or malfunctions.
Tightening too hard causes the short-circuit due to the damage of the screw
or the inverter.
Note 3) When using 4~20mA or 0~20mA signal in frequency setting, always connect
the resistor(200Ħ, 1/4W). (Otherwise, the inverter may be broken.)
Note 4) Please read carefully the specific functions of relevant parameters of each terminal
before attempting to operate the inverter.
Note 5) Common terminals(¢Ù,¢á, ‡N, ‡Q) are connected within the inverter.
Do not ground the common terminal.
22
(Common)
13
14
15
16
VR
+
+
200Ħ
200Ħ
(Common)
1
2
3
4
Start
Forward
SW1 SW2 SW3 SW4 SW5
/
/
Stop
Reverse
(Common)
17
18
19
20
+
D+
D-
Analog output
communication terminal
(0¡«10V)
+
0•`5V
0•`10V
+
4~20mA
0~20mA
5
6
7
8
21
22
23
24
D-
E
D+
Unused
RS485
(Common)
9
10
11
12
E
C1
C2
Open collector output
(TR1¡¢TR2)

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vf100

Table of Contents