[Panel reset function]
When a fault trip occurs, the state cannot be reset with the stop signal input from external devices.
Use STOP SW on the panel to reset the fault trip. If reset lock function is used, it will have the priority.
In addition, reset function is still valid.
Note
•E
If forward run and reverse run signals are turned ON simultaneously, operation state will not
change. If the inverter is stopped and both signals are turned ON simultaneously, the operation
will not start.
P004£ºFrequency setting signal
Used to select frequency setting signal with the operation panel, with signals input from external
devices or with communication command.
Data
Command
setting
signa setting content
state
value
Potentiometer setting
0
Panel
1
2
3
0~5V (voltage signal)
External
4
0~10V (voltage signal)
control
5
4~20mA(Current signal)
6
0~20mA(Current signal)
commu-
7
RS485 communication
nication
Note
•E
If 4~20mA or 0~20mA signals are used, always connect a "200Ħ resistance" between terminals
No.14 and 15. (If the 200Ħ resistance is not connected, the inverter could be damaged.)
•E
When frequency setting signal is set to the data other than "1" and "7", the inverter will start or stop
divided by setting value of "P101: OV stop function select.
If OV stop function is set to be invalid, parameter P101 should be set to "0000"
(OV stop function select: Refer to page 111)
64
Operation method and control terminal connection diagram
Potentiometer on the panel
MAX: maximum frequency (Refer to P005 and P008)
MIN: minimum frequency (or OV stop)
Digital setting
Setting in "frequency setting mode (Fr)".
Terminals No.13, 14, and 15 (Center of potentiometer is
Potentiometer
connected to No.14)
Terminals No.14 and 15(14: +, 15: -)
Terminals No.14 and 15(14: +, 15: -)
Terminals No.14 and 15(14: +, 15: -) 200Ħ is connected
between 14 and 15.
Terminals No.14 and 15(14: +, 15: -) 200Ħ is connected
between 14 and 15.
Make the frequency command input by communication valid.
Related
P036~P040
parameters
Related
P005, P008
¡«
P101
P104
parameters