15. Maintenance and Inspection

!
Caution
¡ñ Wait at least 5 minutes after turning the input power OFF before starting maintenance
¡ñ Maintenance, inspection and part replacement must be done by qualified persons.
!
Note
¡ñ Have electric company periodically tighten the terminal screws.

1. Precautions for inspections

•E When measuring the insulation between the power line and motor line, always disconnect the
wires connected to the inverter first. Do not perform a megger test on the control circuit.
•E The inverter is mainly configured of semiconductor elements. So, daily inspections must be
carried out to prevent the effect of the working environment such as the temperature, humidity,
dust and vibration, to prevent problems that occur due to the passage of part usage and part life.
The standard replacement term that apply when the inverter is used in a general environment
(ambient average annual temperature 30¡æ, load rate of 80% or less, and 12 working hours or
less a day) are given in the following table.

2. Inspection Items

1) Daily inspection:
2) Periodic inspection: Check all locations where inspection can only be performed when the

3. Parts Replacement

Wear fault (lifetime)...The lifetime is greatly dependent on the installation conditions.
1) For example: The lifetime of a relay depends on the wear condition of its contact surfaces.
The contact current and load inductance are major factors.
2) The capacitor inside the inverter is used mainly as a smoothing filter and its lifetime varies
greatly with temperature as internal chemical reactions take place. Generally, when the
temperature of the aluminum electrolytic capacitor increases by 10¡æ, the life is halved.
Thus, the temperature determines the inverter life span.
If the inverter is used at high temperatures, the aluminum electrolytic capacitor could wear out
before the other parts. In this case, the capacitor must be replaced to extend the inverter's life.
Part name
Cooling fan
Smoothing capacitor
Relays
¡ô Contact us if you need part replacement or repairs.
200
and inspection.
Failure to do so could lead to electric shock.
[Remove all metal personal belongings (watches, bracelets, etc.) before starting work.]
(Use tools treated with insulation.)
Failure to do so could lead to electric shock or injury.
Loosening of the terminal screws could lead to overheating or fire.
Check that the inverter is operating as intended.
Check the input and output voltages of the inverter during operation
using a multimeter.
inverter is stopped and where periodic inspection is required.
Standard
replacement
2 or 3 years
Replace with a new part
5 years
Investigate and replace with new part if necessary.
Investigate and replace with new part if necessary.
Replacement procedure