Product Description
Components
Cabinet
The MS-9600 cabinet is red with a navy blue front overlay.
The backbox provides space for two batteries (up to 18 Amp
Hour). Ample knockouts are provided for system wiring. Also
included is a standard dress panel, which mounts to the inside
of the cabinet (required by ULC for Canadian applications).
The dress panel must be installed to meet FM requirements.
Batteries
The MS-9600 cabinet provides space for two batteries (up to 18 Amp Hour). Batteries
larger than 18 Amp Hour up to 25 Amp Hour require use of the Fire•Lite BB-26 or
similar UL listed battery cabinet. The CHG-75 can be used for charging 25 to 75 AH
batteries and the BB-26 can be used for housing the batteries. The CHG-120F can be
used for charging 25 to 120 AH batteries and the BB-55F can be used for housing the
batteries. Batteries must be ordered separately.
1.6.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC
Signaling Line Circuit (refer to the SLC Wiring Manual for detailed information on
device installation, wiring and operation). This allows the control panel to continually
process the information to determine the status (alarm, trouble, maintenance or normal)
of each detector. Each detector responds to an SLC address that is set in the detector
head using built-in rotary decimal switches with the ability to select up to 159
addresses. Note that a blinking LED on an intelligent detector indicates
communication between the detector and the control panel. Refer to the Fire•Lite
Device Compatibility Document for a list of approved detectors.
Smoke Detectors (Photoelectric)
The SD350 and SD355 are intelligent, addressable low profile photoelectric smoke
detectors which provide smoke sensing technology. The SD350T and SD355T include
a 135
o
fixed thermal sensor. The AD350and AD355 are multicriteria photoelectric
smoke detectors with heat sensing capabilities and automatic drift compensation.
Smoke Detector (Ionization)
The CP350 and CP355 are intelligent, addressable low profile ionization smoke
detectors which measure the level of combustion products in their chambers using the
'ionization principle.'
Smoke Detector (Duct)
The D350P is an intelligent, addressable photoelectric duct smoke detector. The
D350RP includes an alarm relay.
Heat Detectors
The H350 and H355 are intelligent heat detectors with thermistor sensing circuits for
fast response, designed to provide open area protection with 50 foot (15 m) spacing
capability. The H350R and H355R incorporate a thermal Rate-of-Rise circuit of 15
o
F
(9.4
o
C). The H355HT is a high temperature heat detector rated for 190
o
F.
Detector Bases
The B501BH is a standard sounder base and the B501BHT is a temporal tone sounder
base for intelligent, addressable smoke detectors.
The B224RB is a relay base with one Form-C relay for intelligent, addressable smoke
detectors. It may be used to control auxiliary functions.
The B224BI is an isolator base for intelligent, addressable smoke detectors. It
functions similar to the I300 isolator module which allows loops to operate under fault
conditions and automatically restore when the fault is removed.
18
MS-9600 PN 51335:E 7/9/03