7-6-19 Input Error Output (sero)

Function
Communications
Settings
See Also

7-6-20 Cold Junction Compensation Method (cjc)

Function
Communications
Settings
164
Condition: The Alarm 1 must be allocated for control output or auxiliary
output. Analog output models only.
• This parameter sets whether to output only the alarm 1 output or whether
to output an OR of the alarm 1 output and sensor error alarm output when
an alarm 1 output is allocated in control or auxiliary output.
• When the sensor error alarm output is enabled (on), alarm 1 for ch1 will
turn ON when a sensor error occurs in a ch1 input, and alarm 1 for ch2
will turn ON when a sensor error occurs in a ch2 input.
• Set the input alarm output to OFF when moving to the initial setting level,
advanced function setting level, or communications setting level.
• This parameter is supported by analog output models only.
ch
Variable type
Shared
C3
Setting range
00000000H(0): Sensor error alarm output disabled (off)
00000001H(1): Sensor error alarm output enabled (on)
• Related Parameters
"Control Output 1 Allocation," and "Control Output 2 Allocation" (initial setting
level) (page 148)
"Auxiliary Output 3 Allocation," and "Auxiliary Output 4 Allocation" (initial set-
ting level) (page 149)
Condition: Input type must be thermocouple or infrared temperature
sensor.
• Specifies whether cold junction compensation is to be performed inter-
nally by the Controller or to be performed externally when the input type
set value is No. 0 to 15, 17 or 18.
• The cold junction compensation external setting is valid when the temper-
ature difference is measured using two thermocouples or two ES1As.
• Setting changes to "cold junction compensation method" must be enabled
by executing a software reset or by turning ON the power again.
ch
Shared
C3
Setting range
00000000H to 00000001H
0: External (off)
1: Internal (on)
Address
003D or 013D
Variable type
002E or 012E
Section 7-6
Default
0: Sensor error alarm
output disabled
Address
Unit
Default
-
1: Internally