Alarm Outputs
Alarm 3
34
2.
Operation for set value 1 (upper and lower limit alarms) would be as follows:
Case 1
Case 2
L
L
H SP
SP
H < 0, L > 0
H > 0, L < 0
|H| < |L|
|H| > |L|
3.
Operation for set value 4 (upper and lower limit ranges) would be as follows:
Case 1
Case 2
SP L
L
H
SP
H < 0, L > 0
H > 0, L < 0
4.
Set value 5 (upper and lower limit alarms with standby sequence):
For upper and lower limit alarm cases in the above diagram, hysteresis is always
OFF for cases 1 and 2 if the upper and lower limits overlap. Hysteresis is always
OFF for case 3.
5.
Set value 5 (upper and lower limit alarms with standby sequence):
Hysteresis is always OFF if the upper and lower limits overlap.
6.
Refer to 4-2 Alarm Hysteresis for information on standby sequences.
Set value
Alarm type
0
Alarm function OFF
1
upper and lower limit (devia-
tion)
2
Upper limit (deviation)
3
Lower limit (deviation)
4
Upper and lower limit range
(deviation)
5
Upper and lower limit alarm
with standby sequence (devi-
ation)
6
Upper limit alarm with
standby sequence (deviation)
7
Lower limit alarm with
standby sequence (deviation)
Case 3
H
H
L
SP
H
L
SP
H
L
SP
Case 3
H
H
SP
L
H
L
SP
SP
H
Alarm output operation
When alarm value
X is positive
Output OFF
X X
ON
OFF
ON
OFF
X
ON
OFF
SP
X X
ON
OFF
X X
ON
OFF
ON
OFF
X
ON
OFF
SP
Section 3-8
H < 0, L < 0
H < 0, L > 0
|H| > |L|
H > 0, L < 0
|H| < |L|
H < 0, L < 0
H < 0, L > 0
|H| > |L|
H > 0, L < 0
|H| < |L|
L
When alarm value
X is negative
Always ON.
SP
X
X
ON
OFF
SP
SP
X
ON
OFF
SP
Always OFF.
SP
Always OFF.
SP
X
X
ON
OFF
SP
SP
X
ON
OFF
SP