Variable Area Map
Variable
Address
ch
type
C3
000B
1
000C
000D
000E
-
000F
Setting data name
Alarm 1 type
Alarm 2 type
Alarm 3 type
Control output 1 alloca-
tion
Control output 2 alloca-
tion
00000000H (0):
No alarm function
00000001H (1):
Upper and lower limit alarm
00000002H (2):
Upper limit alarm
00000003H (3):
Lower limit alarm
00000004H (4):
Upper and lower limit range alarm
00000005H (5):
Upper and lower limit alarm with standby
sequence
00000006H (6):
Upper limit alarm with standby sequence
00000007H (7):
Lower limit alarm with standby sequence
00000008H (8):
Absolute value upper limit alarm
00000009H (9):
Absolute value lower limit alarm
0000000AH (10): Absolute value upper limit alarm with standby
sequence
0000000BH (11): Absolute value lower limit alarm with standby
sequence
Same as for alarm 1 type
Same as for alarm 1 type
00000000H (0):
Heating control output for ch1
00000001H (1):
Cooling control output for heating/cooling con-
trol for ch1
00000002H (2):
Alarm 1 and HB alarm OR output for ch1 (See
note 1.)
Alarm 1 and sensor error alarm OR output for
ch1 (See note 2.)
00000003H (3):
Alarm 2 output for ch1
00000004H (4):
Alarm 3 output for ch1
00000005H (5):
Heating control output for ch2
00000006H (6):
Cooling control output for heating/cooling con-
trol for ch2
00000007H (7):
Alarm 1 and HB alarm OR output for ch2 (See
note 1.)
Alarm 1 and sensor error alarm OR output for
ch2 (See note 2.)
00000008H (8):
Alarm 2 output for ch2
00000009H (9):
Alarm 3 output for ch2
0000000AH (10): SP transfer output for ch1 (See note 2.)
0000000BH (11): Ramp SP transfer output for ch1
(See note 2.)
0000000CH (12): PV transfer output for ch1
(See note 2.)
0000000DH (13): Heating MV transfer output for ch1
(See note 2.)
0000000EH (14): Cooling MV transfer output for ch1
(See note 2.)
0000000FH (15): SP transfer output for ch2
(See note 2.)
00000010H (16): Ramp SP transfer output for ch2
(See note 2.)
00000011H (17): PV transfer output for ch2
(See note 2.)
00000012H (18): Heating MV transfer output for ch2
(See note 2.)
00000013H (19): Cooling MV transfer output for ch2
(See note 2.)
Same as for control output 1 allocation
Section 5-10
Description
95

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents