Using Copy Mode; Parameter Copy Operations - Omron E5ZN Operation Manual

Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Using Copy Mode

6-5
Using Copy Mode
6-5-1

Parameter Copy Operations

Upload (Temperature
Controller to Setting
Display Unit)
1,2,3...
Download (Setting
Display Unit to
Temperature Controller)
1,2,3...
118
1. Press the COPY Key for at least one second to move to the copy mode.
2. Use the Up and Down Keys to select "UP" on the No. 2 display. Press the
UNIT Key to select the unit number for the upload.
Any unit number from 0 to F and "-" (All units) can be selected.
3. Press the Level Key for at least one second to start the upload.
Note a) "Up" will flash on the No. 2 display during the upload.
b) The mode will return automatically to the operation level when the upload
has been completed.
1. Press the COPY Key for at least one second to move to the copy mode.
2. Use the Up and Down Keys to select "DOWN."
The possible selections are "UP" and "DOWN."
3. Press the UNIT Key to select the unit number for the download.
Any unit number from 0 to F can be selected.
However, the unit number for any units without uploaded data will not be
displayed.
Also, the selection operation will not be possible if the uploaded informa-
tion was uploaded from all units. The UNIT display will be "-".
Note For example, to download setting data from unit number 1 to unit number 2,
change the unit number of unit number 2 from 2 to 1, and change the number
of unit number 1 to another unit number or disconnect the socket connected
to unit number 1. Be sure that there is only one Unit with the same Unit num-
ber on the network at any one time.
4. Press the Level Key for at least one second to start the download.
Note a) Control must be stopped to download data. The copy operation will not be
possible in RUN mode.
b) "Down" will flash on the No. 2 display during the download.
c) The mode will return automatically to the operation level when the down-
load has been completed.
d) To download to all Temperature Controllers, use the same configuration
as when the data was uploaded. Downloading is not possible in the fol-