Omron E5ZN Operation Manual
Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Advertisement

Table of Contents
loading

Summary of Contents for Omron E5ZN

  • Page 2 E5ZN Temperature Controller Operation Manual Revised November 2005...
  • Page 3  OMRON, 2001 All rights reserved. No part of this publication may be reproduced, stored in a retrieval system, or transmitted, in any form, or by any means, mechanical, electronic, photocopying, recording, or otherwise, without the prior written permission of OMRON.
  • Page 4 Engineering units (See note.) Channel Note Scaled data is expressed in ° C, m, g, and other engineering units. EU is used as the minimum unit for engineering units For example, the smallest unit of 50.02 (m) is 0.01 (m) and 0.01 is thus one EU.
  • Page 5: Table Of Contents

    Using Heater Burnout Alarm (HBA) ........
  • Page 6 SECTION 7 Parameters ........125 Conventions Used in this Chapter .
  • Page 7 Index.........
  • Page 9: About This Manual

    Section 2 describes mounting, wiring, and other preparatory work that must be done before the E5ZN can be used. Section 3 describes the basic settings required by the E5ZN. Section 4 describes scaling, SP ramp, and other functions to enable maximum use of the E5ZN func- tions. Section 5 describes performing communications for the E5ZN.
  • Page 11 Application Precautions ........
  • Page 12 OMRON representative before applying a Temperature Controller to the above mentioned applications. Application Precautions !WARNING Do not touch the terminals while the power is ON. Doing so may cause an electric shock. !WARNING It may be necessary to install a power supply breaker to turn OFF the power supply before working on the Temperature Controller.
  • Page 13 Application Precautions !Caution Tighten the terminal screws properly. Tighten them to a torque of 0.40 to 0.56 N·m. !WARNING To maintain safety in the event of a Temperature Controller malfunction, always take appropriate safety measures, such as installing an alarm on a separate line to prevent excessive temperature rise.
  • Page 14 • Places directly subject to heat radiated from heating equipment • Places subject to intense temperature changes • Cleaning: Do not use paint thinner or the equivalent. Use standard grade alcohol to clean the Temperature Controller. • Install DIN track vertically.
  • Page 15 Front Panel Names ........
  • Page 16: Name And Function Of Parts

    • The Terminal Unit and the Temperature Controller Module can be sepa- rated, making wiring and maintenance of the E5ZN easier. • Space and wiring can be reduced by using an Expansion Terminal Unit when connecting two or more E5ZN Controllers to the same host.
  • Page 17: Display

    5. SUB1, SUB2 (auxiliary output 1, auxiliary output 2) Lit when auxiliary outputs 1 or 2 is ON. Note There is no display on the front panel for SUB3 and SUB4 (auxiliary output 3 and aux- iliary output 4) of analog output models.
  • Page 18: I/O Configuration And Main Functions

    Aux. output 4 Event input Heating MV Event input transfer output (one) (one) Cooling MV transfer output Default Note Refer to Output Allocations on page 26 for the combinations of functions that can be allocated to the control and auxiliary outputs.
  • Page 19: Main Functions

    (open collector) Current output models (E5ZN-2C@F03@-FLK): Linear current output • Set the alarm type and alarm value, or set upper- and lower-limit alarms. Alarms • If necessary, a more comprehensive alarm function can be achieved by setting the “standby sequence,” “alarm hysteresis,” and “close in alarm/ open in alarm”...
  • Page 21: Preparations

    Assembling Units ........
  • Page 22: Installation

    Assembling Units Joining Terminal Units Up to 15 Expansion E5ZN- SCT18S-500 Terminal Units can be connected to Together a basic E5ZN-SCT24S-500 Terminal Unit. Two Terminal Units can be connected by joining the side connector on each Terminal Unit. Side connectors...
  • Page 23 Mounting to DIN Track Mounting the Unit Pull the hook down on the bottom, latch the top hook onto the track, push the Unit until the hook locks onto the track, and then push the hook back up to lock the Unit in place.
  • Page 24 Installation Section 2-1 Removing the Unit Use a flat-blade screwdriver to pull down the hook and lift the Unit from the bottom. Flat-blade screwdriver Mounting End Plates Always mount end plates to both ends of the E5ZN Temperature Controllers. For only one...
  • Page 25 Position the DIN track vertical to the ground. Mounting the E5ZN Mounting the Module Module Line up the Module with the guides on the Terminal Unit and push firmly into place. Line up with guides and push firmly until the Module clicks into place.
  • Page 26 Installation Section 2-1 Covers When wiring, open the E53-COV12 Terminal Cover attached to the E5ZN- SCT24S-500 Terminal Unit or the E53-COV13 Terminal Cover attached to the E5ZN-SCT18S-500 Terminal Unit. When wiring has been completed, close the cover until it clicks shut.
  • Page 27: Using The I/O Section

    E5ZN-2T@H03@-FLK 2-2-2 Precautions when Wiring • Separate signal leads and power lines in order to protect the E5ZN and its lines from external noise. • We recommend using solderless terminals when wiring the E5ZN. • Tighten the terminal screws using a torque between 0.40 and 0.56 N·m.
  • Page 28 11 and 12 when channel 1 is not used. • For Pt: Connect a resistance of 100 to 125 Ω between terminals 4 and 5 when channel 2 is not used, or between terminals 10 and 11 when channel 1 is not used.
  • Page 29 Using the I/O Section Section 2-2 • Terminals 7 and 8 are for control output 1 (OUT1) and terminals 1 and 2 Control Output 1/2 are for control output 2 (OUT2). 4-20mADC/ 4-20mADC/ OUT1 OUT2 OUT1 OUT2 OUT1 OUT2 0-20mADC...
  • Page 30 CT Input • When the heater burnout alarm is used, connect a current transformer (CT) across terminals 16 and 17 for channel 1 and terminals 16 and 18 for channel 2 (no polarity). • Use E54-CT1 or E54-CT3 Current Transformers.
  • Page 31 • When communicating with a host, connect across terminals 23 and 24. Communications B(+) RS-485 A( ) • The RS-485 connection can be either one-to-one to one-to-N. Up to 16 Temperature Controllers can be connected in one-to-N systems. • Keep the total cable length to 500 m maximum. E5ZN-SCT24S-500 ■ Isolation The E5ZN terminals are electrically isolated in the blocks shown below.
  • Page 32 Using the I/O Section Section 2-2 • Attach a terminator to both ends of the transmission path, including the host. • The terminator specifications are as follows: Terminator 100 to 125 (1/2 W) • Use an RS-232C/RS-485 Converter when connecting personal comput- ers with an RS-232C port.
  • Page 33: Installation Precautions

    55 ° C. The life of electronic equipment like Temperature Controllers is influenced not only by the life determined by the relay switching count but also by the life of internal electronic components. The service life of components is dependent on the ambient temperature: The higher the ambient temperature becomes, the shorter the service life becomes, and vice versa.
  • Page 34: Enclosure Ratings

    Installation Precautions Section 2-3 2-3-4 Enclosure Ratings The enclosure ratings are shown in the following table. The E5ZN is not water- proof. Temperature Controller IP00 Module Terminal Units IP00...
  • Page 35: Temperature Control Settings

    Setting Output Specifications ........
  • Page 36: Setting The Input Type

    3-1-1 Input Type To set the input type to a K thermocouple from 20.0 to 500.0 ° C, use host communications or the E5ZN-SDL Setting Display Unit to set 1 as the set value for the input type.
  • Page 37: Selecting Centigrade/Fahrenheit

    The same temperature unit is used for both channel 1 and channel 2. To use ° C, use host communications and set 0 as the temperature unit or use the E5ZN-SDL Setting Display Unit and set c.
  • Page 38: Selecting Pid Control Or On/Off Control

    These PID constants can be set by autotuning or manual setup. ON/OFF Control In ON/OFF control, the control output is turned ON when the PV is lower than the current SP, and the control output is turned OFF when the PV is higher...
  • Page 39: Setting Output Specifications

    • Set the output period (control period). Though a shorter period provides better control performance, we recommend setting the control period to 20 seconds or more when using a relay output for heater control (to increase the effective life of the relay). If necessary, readjust the control period according to the results of trial operation with the control period parameters set to their defaults.
  • Page 40: Output Allocations

    Terminals 14 and OR output Note When “Cooling control output for ch 1” has been set for an output, ch 1 performs heat- ing/cooling control. When “Cooling control output for ch 2” has been allocated to the output, ch 2 performs heating/cooling control.
  • Page 41 PV transfer output Terminals 16 and Note When “Cooling control output for ch 1” has been set for an output, ch 1 performs heat- ing/cooling control. When “Cooling control output for ch 2” has been allocated to the output, ch 2 performs heating/cooling control.
  • Page 42: Setting The Sp

    Use host communications or the E5ZN-SDL Setting Display Unit to set the SP. Default is 0 ° C. In this example, the SP will be changed from 0 ° C to 200 ° C. • Use host communications to set the “SP” parameter to “000000C8H (200°C).”...
  • Page 43: Executing On/Off Control

    ON again. This operation is repeated between certain points. How much the temperature must fall in rela- tion to the SP before control output turns ON again is determined by the “heating hysteresis” parameter. Also, whether the manipulated variable (MV) must be increased or decreased in response in an increase or decrease in the PV is determined by the “direct/reverse operation”...
  • Page 44: Setup

    Executing ON/OFF Control Section 3-6 3-6-2 Setup To execute ON/OFF control, set the SP, the PID/OnOff parameter, and the hysteresis. Setting ch1 to ON/OFF Use host communications or the E5ZN-SDL Setting Display Unit to make the following settings. Control with an SP of 200 °...
  • Page 45: Determining Pid Constants: Autotuning And Manual Setup

    STOP,” “AT execute/stop,” and “auto/manual” parameters can be changed. No other settings can be changed. • If “RUN/STOP” is set to “STOP” during execution of autotuning, autotun- ing and operation will stop. Autotuning will not start again even if “RUN/ STOP” is set to “RUN” again.
  • Page 46: Manual Setup

    PID parameters are set in the “proportional band” (P), “in- tegrated time” (I), and “derivative time” (D) parameters. When PID constants I (integral time) and D (derivative time) are set to 0, control is executed according to proportional operation. The default SP becomes the center value of the proportional band.
  • Page 47: Alarm Outputs

    11 (See Absolute-value lower limit note 6.) with standby sequence Note With set values 1, 4, and 5, the upper and lower limits can be set independently for each alarm point and are expressed as “L” and “H.”...
  • Page 48 Set value 5 (upper and lower limit alarms with standby sequence): For upper and lower limit alarm cases in the above diagram, hysteresis is always OFF for cases 1 and 2 if the upper and lower limits overlap. Hysteresis is always OFF for case 3.
  • Page 49: Alarm Values

    Absolute-value lower limit with standby sequence Use host communications or the E5ZN-SDL Setting Display Unit to set the alarm type separately for each alarm for alarms 1 to 3. Defaults are “2: Upper limit.” Set the alarms separately for each channel. 3-8-2 Alarm Values Alarm values are indicated by “X”...
  • Page 50: Using Heater Burnout Alarm (Hba)

    • Be sure to connect the CT to the E5ZN, and pass the heater lead through the CT hole. • Turn ON the heater at the same time as or before turning the E5ZN. If the heater is turned ON after turning the E5ZN, the heater burnout alarm will activate.
  • Page 51: Calculating The Detection Current Value

    (When the resultant current is less than 2.5 A, detection is unstable.) • The setting range is 0.1 to 49.9 A. Heater burnout is not detected if the set value is 0.0 or 50.0. If the set value is 0.0, the heater burnout alarm is turned OFF, and if the set value is 50.0, the heater burnout alarm is turned...
  • Page 52: 3-10 Starting And Stopping Control

    2. Using the E5ZN-SDL Setting Display Unit. 3. Using an external contact for an event input. • Set the operation status after the power supply for the E5ZN has been Operation after Turning turned ON. Choose one of the following two statuses.
  • Page 53: 3-11 Operating Precautions

    Section 3-11 3-11 Operating Precautions 1,2,3... 1. About four seconds is required for outputs to turn ON after the power is turned ON. Take this into consideration when the Temperature Controller is incorporated into a sequence circuit. 2. The Temperature Controller may be subject to the influence of radio inter-...
  • Page 55: Settings Used Only When Required

    Standby Sequence........
  • Page 56: Shifting Input Values

    PV. An input shift can be applied if the measurement value requires shifting. • Two types of input shift can be used. A one-point shift is used to simply shift the measurement value. For a two-point shift, the shift amount for the lower limit and upper limit are set separately and both the measurement values and the slope are shifted.
  • Page 57: Calculating Input Shift Values For Non-Contact Sensors

    One-point Shift 1,2,3... 1. In the configuration shown in Figure 1, bring the SP to near the value at which the temperature of the control target is to be controlled. Let's as- sume that the control target temperature (C) and the control target temper- ature (B) are the same.
  • Page 58 1,2,3... 1. The Controller readout will be shifted at two points, near room temperature and near the value at which the temperature of the control target is to be controlled. For this reason, bring the control target temperature to near room temperature and to near the SP, and check the control target temper- ature (B) and Controller readout (A) at both points.
  • Page 59 We will assume that when the room temperature X1 is 25 ° C, the readout on the Controller Y1 is 40 ° C, and when the temperature near the SP X2 is 110 ° C, the readout on the Controller Y2 is 105 ° C.
  • Page 60: Alarm Hysteresis

    • The standby sequence allows alarm outputs to be temporarily disabled until the temperature leaves the alarm range (i.e., until an alarm condition does not exist). Once the alarm range has been left, the alarm output will then operate whenever the alarm range is entered.
  • Page 61: Close In Alarm/Open In Alarm

    • The close in alarm/open in alarm status can be set independently for each alarm. • The close in alarm/open in alarm settings are set in the “Alarm 1 to 3 open in alarm” parameters. • Default is “0: Close in alarm.”...
  • Page 62: Setting Scaling Upper And Lower Limits (Analog Input)

    Upper limit (95.0%) Lower limit (10.0%) Input (mV) In this example, the scaling upper and lower limits are set so that inputs 0 to 50 mV are scaled to 10.0% to 95.0%. Scaling upper limit: 950 Scaling lower limit: 100...
  • Page 63: Executing Heating And Cooling Control

    • The default allocation is “heating control output.” Dead Band The dead band is set with the SP as its center. The dead band width is set in the “dead band” parameter in the adjustment level. Setting a negative value produces an overlap band.
  • Page 64: Using The Event Input

    Using the Multi-SP The multi-SP function is used to switch between two SPs. Different SPs are set in advance for SP 0 and SP 1 and the event input contact signals or E5ZN- SDL Setting Display Unit is used to switch them.
  • Page 65 Using the Event Input Section 4-5 Using Communications The SP can be selected using the communications parameters shown in the following table. Multi-SP SP 0 SP 1 Note The SP can be switched independently for ch 1 and ch2. Using Key Operations...
  • Page 66: Setting The Sp Upper And Lower Limit Range

    SP limit if it goes outside the SP limit range. For example, If the SP upper limit is changed to 150 ° C when the SP is 200 ° C, the SP upper limit was 300 ° C, and the SP lower limit is 100 ° C, the SP will have gone outside the existing SP limit range of 100 °...
  • Page 67: Sp Ramp Function: Limiting Sp Change Rate

    4-7-1 SP Ramp The SP ramp function controls the rate of change of the SP. If a change larger than the rate of change is specified when the SP ramp function has been enable, changes in the SP will be limited as shown below. Thus, when changes are made to the SP with the SP ramp function enabled, control is performed according to the rate of change rather than the target value.
  • Page 68: Key Protection

    Section 4-8 Key Protection 4-8-1 Key Protect Function The protect function limits the settings that can be changed to prevent inad- vertently changing settings. There are three protect mechanisms: “Communications writing” prohibits set- ting changes from host communications, while “operation/adjustment protec- tion”...
  • Page 69 Key Protection Section 4-8 Setting Change This protect level protects the setup from being changed by operating the keys on the front panel. Protection wtpt Set value Description Setup can be changed by key operation. Setup cannot be changed by key operation. (The protect level can be changed.)
  • Page 70: Manual Mode

    Auto/Manual • If the “auto/manual” operation command is used by host communications to set “01: manual (ch1)” or “11: manual (ch2),” the E5ZN will operate in manual mode. • If ON/OFF control is selected, operation cannot be switched to manual mode.
  • Page 71: Manual Manipulated Variable

    (control operating) and STOP (control stopped). STOP • Even if the manual manipulated variable is set to STOP during output in manual mode, the operation status will not change and the output of the manual manipulated variable will continue. (Refer to the following dia- gram.)
  • Page 72: 4-10 Reading Temperatures For Multiple E5Zn Units

    Temperature Controller, making it difficult to obtain con- current data. The PV hold function can be used with the E5ZN to ensure that the data is concurrent to within 500 ms. To read present temperatures from all Temperature Controllers, the PV is read in order from Unit No.
  • Page 73: 4-11 Remote Pv Mode

    2. Set the cycle for communications data sent from the external sensor to “re- mote PV communications wait time.” This setting affects both channels. If the refresh cycle for data from the external sensor is longer than the “re- mote PV communications wait time,” the E5ZN will determine that the ex- ternal sensor has been disconnected, and an input error will occur.
  • Page 74: 4-12 Using Transfer Output

    (initial setting level) can be scaled to the output range for the transfer output (4 to 20 mA DC or 0 to 20 mA DC for control output 1 and 2, and to 1 to 5 VDC or 0 to 5 VDC for auxiliary output 3 and 4).
  • Page 75 Using Transfer Output Section 4-12 Application Example ■ Example 1: Recording ch1 Input between 0 and 200 °C Using a Recorder Temperature Controller: E5ZN-2C@F03TC-FLK (current output, thermocou- ple input) Recorder: E55A-F@ Sensor: E52-CA15A D=3.2 NETU @M (K thermocouple, sheath, protective tubing dia. 3.2 mm, protective...
  • Page 76 Current output type (initial setting level): 0 (4 to 20 mA DC) Meter Setting Example: Inputs for 4 to 20 mA DC are scaled to 0.0 to 100.0 ° C. Input type (initial setting level: in-t): 4 to 20 mA DC (4-20) Scaling input value 1 (initial setting level: inp.1): 4 mA (4.00)
  • Page 77 Read Monitor Value ........
  • Page 78: Communication Protocols

    Command and response frames are transmitted as follows: Host PC Temperature Controller Allow a minimum wait time of 5 ms from when the host PC receives the re- sponse from the Temperature Controller until the host sends the next com- mand.
  • Page 79: Data Format Structure

    30H 30H 30H 30H 30H 30H 35H 30H 30H BCC = 30H ⊕ 30H ⊕ 30H ⊕ 30H ⊕ 30H ⊕ 30H ⊕ 35H ⊕ 30H ⊕ 30H ⊕ 03H = 36H ⊕ : XOR (exclusive OR) operation Note How to Determine the BCC: The BCC is determined by XOR operation on a byte-by-byte basis of the values within the range from the node number field to the ETX field.
  • Page 80: Response Frame

    “00” 1 byte Note The Temperature Controller will not respond to any command frame that does not end in the ETX and BCC. Code indicating the start of a response frame (02H). Be sure to place this code in the first byte of the response frame.
  • Page 81: Structure Of Command/Response Text

    The command/response text constitutes the main body of a command/ response frame. The structure of the command/response text is described below. Command Text The command text consists of the MRC (Main Request Code) and the SRC (Sub Request Code), followed by the required data. FINS-mini Node...
  • Page 82: Variable Area

    The variable area is not used for operation commands or for reading Control- ler attributes. E5ZN Microcomputer Variable area Data reading/writing To specify the position of a variable in the variable area, use the variable type and address. Address 0000 0001 0002 0003 013D 013E 013F Variable type Variable The address is a 4-digit hexadecimal code.
  • Page 83: Read From Variable Area

    Specify the read start address. Bit position Not used for E5ZN. Always set this item to “00.” No. of elements Set this item to the quantity of variables that are to be read (up to 6). Not required for multiple reads. Response Response Text...
  • Page 84: Write To Variable Area

    Bit position Not used for E5ZN. Always set this item to “00.” No. of elements Set this item to the quantity of variables that are to be written (up to 6). Not required for multiple writes. Data to be written Place the desired data in this field.
  • Page 85: Operation Commands

    Operation Commands Section 5-7 Operation Commands To send an operation command to the Temperature Controller, set the items in the command text as follows: Command Command Text Command Related code information “30” “05” 2 bytes Item Description MRC/SRC Specify the FINS-mini operation command (operation com- mand service).
  • Page 86 Command codes for which the related information is indicated as “00” or “10,” or “01” or “11” use the same command for both ch1 and ch2. Either value in the relat- ed information can be used. (The result will be the same.)
  • Page 87: Setting Areas

    At power-ON, the Temperature Controller is set in setting area 0. To move to setting area 1, use the “move-to-setting area 1” command. To return to setting area 0, turn the power OFF and ON again, or use the “software reset” com- mand.
  • Page 88: Commands And Responses

    PV hold value “0106” PV hold value This command reads the current PV, status, or other monitor values. If the number of elements is set between “2” and “6”, consecutive address monitor values can be read. If the Temperature Controller is in setting area 1 when the command is received, it returns a response with the “unknown”...
  • Page 89: Read Setting Data

    Setting data for setting area 1 “0100” to “0101” This command reads setting data. If the number of elements is set between “2” and “6”, consecutive address setting data can be read. Refer to 5-10 Variable Area Map for information on specifying variable types and addresses.
  • Page 90: Multiple Reads Of Monitor Values/Setting Data

    Refer to 5-10 Variable Area Map for information on specifying variable types and addresses. This command can be used in either setting area 0 or 1. No data will be read if an area type error or parameter error occurs in any of the data. Variable...
  • Page 91: Write Protect Level Setting Data

    6-3 Setup Level Configuration and Front Panel Keys . This command can be used in setting area 0 only. If the Temperature Control- ler is in setting area 1 when the command is received, it returns an error. Before executing the command, use operation commands to enable writing and to enter the protect level.
  • Page 92: Write Setting Data

    “write mode” operation command to set the write mode to “backup.” If it is not set to backup mode, the setting data will not be stored when the power is turned OFF. Refer to 6-3 Setup Level Configuration and Front Panel Keys for details on the operation/adjustment level.
  • Page 93: Multiple Writes Of Setting Data

    Refer to 5-10 Variable Area Map for information on specifying variable types and addresses. Setting area 1 setting data can be written in setting area 1 only. An error will be returned if this command is executed for setting area 0.
  • Page 94: Communications Writing

    STOP (See note.) This command starts and stops control (RUN/STOP). This command can be used in either setting area 0 or 1. Note These variations of the command are supported by upgraded pulse output models and analog output models only. Response Response code “30”...
  • Page 95: Multi-Sp

    This command switches between SPs that have been set in advance for SP 0 and SP1. “No. of multi-SP uses” must be set to 0 and “Use multi-SP” must be set to ON. This command can be used for either setting area 0 or 1.
  • Page 96: 5-9-11 Write Mode

    Level Configuration and Front Panel Keys for information on operation/adjustment level. When switching from RAM write mode to backup mode, the operation/adjust- ment level setting data is written to internal non-volatile memory. Refer to 6-3 Setup Level Configuration and Front Panel Keys for information on operation/ adjustment level.
  • Page 97: 5-9-12 Ram Data Save

    “00” or “10” This command writes operation/adjustment level setting data to internal non- volatile memory. Refer to 6.3 6-3 Setup Level Configuration and Front Panel Keys for information on operation/adjustment level. This command can be used for either setting area 0 or 1.
  • Page 98: Move To Setting Area 1

    This command can be used in setting area 0 only. If the Temperature Control- ler is in setting area 1 when the command is received, it returns an error. Before executing the command, use an operation command to enable com- munications writing.
  • Page 99: 5-9-16 Auto/Manual

    This command saves the PV when the command was executed in the variable area. This command can be used for setting area 0. If it is used in setting area 1, an operation error will be returned. Before executing the command, use an operation command to enable com- munications writing.
  • Page 100: Parameter Initialize

    “00” or “10” This command returns all settings to the default values. This command can be used for setting area 0. If it is used in setting area 1, an operation error will be returned. Before executing the command, use an operation command to enable com- munications writing.
  • Page 101: Read Controller Attribute

    Not sup- voltage put (sourcing) age output ported output The model name is expressed in 10-byte ASCII. A fixed value of “0048H” (72 bytes) for the buffer size is returned. Response Code Response Error name Description code “1001” Command length over The command is too long.
  • Page 102: 5-9-21 Read Controller Status

    Detected detected Current hold Detected detected Input error Detected detected If the Temperature Controller is in setting area 1 when the command is received, it returns a response with “unknown” related information. Response Code Response Error name Description code “1001”...
  • Page 103: 5-9-22 Echoback Test

    “08” “01” 0 to 23 bytes This command performs an echoback test. The command can be used regardless of the state of the Temperature Con- troller. Data to be checked must not exceed the communications data length. Communication data length...
  • Page 104: 5-10 Variable Area Map

    Variable type C7: Setting data for setting area 1 Allocations for each variable are listed below. A dash (-) in the “ch” column indicates data that is used by both channels. Note This data is used by pulse output models only.
  • Page 105 Alarm output 1 Alarm output 2 Alarm output 3 Note: For pulse output models, the status of these bits shows the status of the corresponding operation indicators. For analog output modes, the status of these bits is undefined (i.e., the bits will not necessarily show the status of the indicators).
  • Page 106 Alarm value 1 FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9) 0005 Alarm upper limit value 1 FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9) 0006 Alarm lower limit value 1 FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
  • Page 107 FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9) 0105 Upper limit alarm value 1 FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9) 0106 Lower limit alarm value 1 FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
  • Page 108 00000011H (17): T ( 199.9 to 400.0°C or 199.9 to 700.0°F) 00000012H (18): U ( 199.9 to 400.0°C or 199.9 to 700.0°F) 0001 Scaling upper limit Scaling lower limit + 1 to 0000270FH (scaling lower limit + 1 to 9,999) 0002 Scaling lower limit...
  • Page 109 00000001H (1): Cooling control output for heating/cooling con- trol for ch1 00000002H (2): Alarm 1 and HB alarm OR output for ch1 (See note 1.) Alarm 1 and sensor error alarm OR output for ch1 (See note 2.) 00000003H (3):...
  • Page 110 00000001H (1): Cooling control output for heating/cooling con- trol for ch1 00000002H (2): Alarm 1 and HB alarm OR output for ch1 (See note 1.) Alarm 1 and sensor error alarm OR output for ch1 (See note 2.) 00000003H (3):...
  • Page 111 α 0025 00000000H to 00000064H (0.00 to 1.00) 0026 MV upper limit Standard: Manipulated variable lower limit + 0.1 to 0000041AH (manipulated variable lower limit + 0.1 to 105.0) Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0) 0027 MV lower limit Standard: FFFFFFCEH to manipulated variable upper limit 0.1...
  • Page 112 Same as for auxiliary output 3 allocation. tion (See note 2.) 0031 OUT1 transfer output FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9) upper limit (See note 2.) 0032 OUT1 transfer output FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9) lower limit (See note 2.)
  • Page 113 Sensor error indicator 00000000H(0): Indicators always not lit (See note 2.) 00000001H(1): Sensor error indicator lit (ch1 only) 00000002H(2): Sensor error indicator lit (ch2 only) 00000003H(3): Sensor error indicator lit (ch1 or ch2) 003C Remote-local logic (See 00000000H(0): Reverse logic note 2.)
  • Page 114 00000011H (17): T ( 199.9 to 400.0°C or 199.9 to 700.0°F) 00000012H (18): U ( 199.9 to 400.0°C or 199.9 to 700.0°F) 0101 Scaling upper limit Scaling lower limit + 1 to 0000270FH (scaling lower limit + 1 to 9,999) 0102 Scaling lower limit...
  • Page 115 00000006H (6): Cooling control output for heating/cooling con- trol for ch2 00000007H (7): Alarm 1 and HB alarm OR output for ch2 (See note 1.) Alarm 1 and sensor error alarm OR output for ch2 (See note 2.) 00000008H (8):...
  • Page 116 00000006H (6): Cooling control output for heating/cooling con- trol for ch2 00000007H (7): Alarm 1 and HB alarm OR output for ch2 (See note 1.) Alarm 1 and sensor error alarm OR output for ch2 (See note 2.) 00000008H (8):...
  • Page 117 α 0125 00000000H to 00000064H (0.00 to 1.00) 0126 MV upper limit Standard: Manipulated variable lower limit + 0.1 to 0000041AH (manipulated variable lower limit + 0.1 to 105.0) Heating/cooling: 00000000H to 0000041AH (0.0 to 105.0) 0127 MV lower limit Standard: FFFFFFCEH to manipulated variable upper limit 0.1...
  • Page 118 Same as for auxiliary output 3 allocation tion (See note 2.) 0131 OUT1 transfer output FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9) upper limit (See note 2.) 0132 OUT1 transfer output FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9) lower limit (See note 2.)
  • Page 119 0000 Remote PV Temperature: According to specified range for each sensor Analog: Scaling lower limit 5% FS to scaling upper limit + 5% FS 0100 Remote PV Temperature: According to specified range for each sensor Analog: Scaling lower limit...
  • Page 121: Using The E5Zn-Sdl

    Names of Parts on the Front Panel ....... . .
  • Page 122: Introduction

    Introduction Section 6-1 Introduction 6-1-1 Outline The E5ZN-SDL Setting Display Unit is used to set and display parameters for E5ZN Temperature Controllers. Using the E5ZN-SDL simplifies the initial settings and maintenance of the E5ZN. 6-1-2 Dimension E5ZN-SDL (84) 48x48 63.7 14.2...
  • Page 123: Preparation

    Note Connections between terminals 4 and 9, 7 and 11, and 8 and 10 are made inside the E5ZN-SDL. Refer to the following connection diagram. Do not connect anything to terminals 1, 2, 5, or 6.
  • Page 124 • Keep the total cable length to 500 m maximum. • Attach a terminator to both ends of the transmission path. Note Communications with the E5ZN-SDL will be cut if the E5ZN-2 connection to the E5ZN- SCT24S-500 is broken The E5ZN Temperature Controller and the E5ZN-SDL are connected by serial communications.
  • Page 125: Names Of Parts On The Front Panel

    E5ZN Temperature Controller is set to a temperature. Indication is determined by the current set value of the “temperature unit” parameter. When this parameter is set to ° C, “c” is displayed, and when set to ° F, “f” is displayed. Operation Indicators 1,2,3...
  • Page 126: Using The Keys

    Displays the E5ZN Temperature Indicator unit number and channel num- ber that will be set and displayed on the E5ZN-SDL. When facing the front panel, the unit number (0 to F) is displayed on the left and the channel number (1 to 2, U) is displayed on the right.
  • Page 127 Copy All settings for the E5ZN Temperature Controller can be read and saved to the E5ZN-SDL. Also, all the settings for the E5ZN Temperature Controller that were saved in the E5ZN-SDL can be written to the E5ZN Temperature Con-...
  • Page 128: Setup Level Configuration And Front Panel Keys

    Controller outputs are stopped when any of these four levels are selected. It is possible to enter copy mode while Controller outputs are being made, but copy operations (e.g., upload, download) can by used only when control has...
  • Page 129 • During operation, the PV, SP, and manipulated variable can be monitored, and the SP, alarm value and upper and lower limit alarms can be moni- tored and modified. • To move the mode to this level, press the Level Key for less than one sec- Adjustment Level ond.
  • Page 130: Initial Setup Examples

    DIP switches. These hardware settings are now set using the setup menus of the E5ZN-SDL. The Level and Mode Keys are used to switch between setup menus, and the amount of time that you hold the keys down determines which setup menu you move to.
  • Page 131 Initial Setup Examples Section 6-4 Typical Example 2 4 (T thermocouple 200 to 400 ° C) Input type: E5ZN unit number: 1 Control method: PID control Channel: Calculate PID constants by autotuning. Alarm type: 2 (upper limit) Alarm value 1:...
  • Page 132: Using Copy Mode

    1. Press the COPY Key for at least one second to move to the copy mode. 2. Use the Up and Down Keys to select “UP” on the No. 2 display. Press the UNIT Key to select the unit number for the upload.
  • Page 133: Copying Parameters From Master To Slaves

    Data uploaded to the E5ZN-SDL can be downloaded only to a Unit whose unit number has been uploaded. Therefore, after copying the Master parameters, change the unit number of the Unit where the data is to be downloaded to the uploaded unit number (Master’s unit number), and then download the param- eter data.
  • Page 134 UNIT COPY 4. The unit number of the Unit to which the data is to be downloaded will change to the uploaded unit number. When uploading has been complet- ed, turn OFF the power and disconnect the Unit (unit number 1) that has been uploaded from the socket or change the unit number to avoid using the same unit number twice during the download.
  • Page 135 9. After copying is completed, turn OFF the power and change the unit num- bers. In this example, turn OFF the power and change unit number 5 to unit number 1, and change unit number 1 to unit number 3.
  • Page 136: List Of Parameters

    The following diagram shows the parameters that can be set from Communication the E5ZN-SDL Setting Display Unit. Some data is not displayed as setting level it is protected or is subject to usage conditions. A password must Communi- be entered for access to the advanced function setting level. cations...
  • Page 137 Derivative Time Value 2 Mode Key Mode Key Alarm Value 3 Mode Key MV Monitor for Heating Mode Key MV Monitor for Cooling Mode Key To top of operation level Note Indicates parameters that are displayed for pulse output models only.
  • Page 139: Parameters

    C/ F Selection (d-u) ........
  • Page 140 7-6-4 Multi-SP Uses (mspu) ........
  • Page 141: Conventions Used In This Chapter

    Display Conditions for Related Parameters The parameters are displayed in the display section of the E5ZN-SDL Setting Display Unit only when the condition for use shown at the top of the section describing the parameter are met. Protected parameters are not be displayed regardless, although the parameters themselves will be enabled.
  • Page 142: Protect Level

    : Can be displayed × : Cannot be displayed and move to other levels not possible Parameter items are not protected when the set value is set to 0. Initial Setting/Communications Protection Moving to the “initial setting level,” “communications setting level” and “advanced function setting level”...
  • Page 143: Operation Level

    “SP upper limit” “SP lower limit” (page 145) 7-3-2 PV/SP Function The PV is displayed on the No.1 display, and the SP is displayed on the No. 2 display. Monitoring range Unit Input range lower limit 10%FS to input range upper limit...
  • Page 144: Multi-Sp (Sp 0 To 1) (M-Sp)

    The ramp function restricts the rate of change in the width of the SP. The set value is displayed when “SP ramp set value” parameter is set. When the SP is out of the preset ramp, the SP is matched to the SP set in the “PV/SP” parameter.
  • Page 145: Run/Stop (R-S)

    Alarm Value 2 (al-2) Alarm Value 3 (al-3) Condition: The alarm type must not be set to no alarm or upper and lower limit alarm (alarms 1 and 2 only). These parameters set the input value “X” in the alarm.
  • Page 146: Alarm Upper Limit Value 1 (Al 1H) Alarm Lower Limit Value 1 (Al 1L)

    Setting range Unit Default FFFFF831H to 00000270FH ( 1999 to 9999) The alarm type must be set to other than no alarm or upper and lower limit alarm (alarms 1 and 2 only). • Related Parameters See Also “Input type” (initial setting level) (page 143) “Scaling upper limit”...
  • Page 147: Alarm Upper Limit Value 2 (Al2H)

    These parameters independently set the upper and lower limit alarm values when the mode for setting the upper and lower limits is selected for alarm 2 type. • These parameters set the upper and lower limits of alarm 2.
  • Page 148: Mv Monitor For Cooling (C-O)

    7-3-11 MV Monitor for Cooling (c-o) The control must be heating and cooling control. This parameter is for monitoring the MV on the cooling side during operation. Function During heating and cooling control, the MV on the cooling side is monitored.
  • Page 149: Adjustment Level

    Use the “AT execute/cancel” operation command. Refer to page 81 for infor- mation. • Normally, this parameter is set to “ off ”. When you press the Up Key, the Example of Use parameter is turned ON and AT is executed.
  • Page 150: Heater Burnout Detection (Hb)

    • This parameter outputs the heater burnout alarm when the heater current Function value falls below this parameter setting. • When the set value is 0.0, the heater burnout alarm will be OFF. When the set value is 50.0, the heater burnout alarm will be ON. Communications...
  • Page 151: Sp 0 (Sp-0) Sp 1 (Sp-1)

    Condition: Refer to the following table for details. Sometimes an error between the SP and the actual temperature occurs. To offset this, a value obtained by adding an input shift value to the input is dis- played as the measurement value and used for control.
  • Page 152: Upper Limit Temperature Input Shift Value (Insh)

    The entire input range is shifted by a fixed rate (one-point shift). If the input shift value is set to 1.0 ° C, the SP is controlled to a value obtained by subtracting 1.0 ° C from the actual temperature.
  • Page 153: Proportional Band (P) Integral Time (I) Derivative Time (D)

    Integral Time (i) Derivative Time (d) Condition: The control must be 2-PID control. These parameters set the PID constants for control. The PID can be automat- ically set by executing autotuning. Function Proportional action:P refers to control in which the MV is proportional to the deviation.
  • Page 154: Cooling Coefficient (C-Sc)

    PID parameters, adjust the proportional band (P) on the cooling side by add- ing the cooling coefficient to control cooling. Function In heating and cooling control, cooling side P is calculated by the following for- mula to set the cooling coefficient: Cooling side P = Cooling coefficient × P (proportional operation)
  • Page 155: Dead Band (C-Db)

    Section 7-4 7-4-10 Dead Band (c-db) Condition: The control system must be heating and cooling control. This parameter sets the output dead band width in a heating and cooling con- trol system. A negative setting sets an overlap band. Function This parameter sets an area in which the control output is 0 centering around the SP in a heating and cooling control system.
  • Page 156: Heating Hysteresis (Hys) Cooling Hysteresis (Chys)

    Function ing hysteresis” parameter cannot be used. • In a heating and cooling control, the hysteresis can be set independently for heating and cooling. Use the “heating hysteresis” parameter to set the heating side hysteresis, and use the “cooling hysteresis” parameter to set the cooling side hysteresis.
  • Page 157: Initial Setting Level

    • This parameter sets the sensor type using a corresponding code. Function • When this parameter is changed, the SP limiter is changed to the default. If the SP limits must be changed, set the “SP upper limit” and “SP lower limit” parameters. Communications...
  • Page 158: Scaling Upper Limit (In-H) Scaling Lower Limit (In-L) Decimal Point (Dp)

    Scaling Lower Limit (in-l) Decimal Point (dp) Condition: The input type must be set to analog input. • These parameters can be used when a voltage input is selected as the Function input type. • When a voltage input is selected as the input type, scaling is performed.
  • Page 159: Sp Upper Limit (Sl-H) Sp Lower Limit (Sl-L)

    • These parameters set the upper and lower limits for the SP setting. The Function SP can be set within the range defined by the upper and lower limit set values in the “SP upper limit” and “SP lower limit” parameters. If existing SP settings are out of the range, they will be changed to either the upper or lower limits (which-ever is closest).
  • Page 160: Heating Control Period (Cp) Cooling Control Period (C-Cp)

    • In a standard control system, use the “heating control period” parameter. • In a heating and cooling control system, the control period can be set independently for heating and cooling. Communications...
  • Page 161: Alarm 1 Type (Alt1) Alarm 2 Type (Alt2) Alarm 3 Type (Alt3)

    “Alarm 1 to 3 hysteresis” (advanced function setting level) (page 158) “Alarm 1 to 3 latch” (advanced function setting level) (page 163) 7-5-9 Control Output 1 Allocation (out1) Function This function assigns the data to be output to the control output 1 terminals (terminals 7 and 8.)
  • Page 162: Control Output 2 Allocation (Out2)

    Heating MV transfer output 00000013H (19) Cooling MV transfer output 7-5-10 Control Output 2 Allocation (out2) Function This parameter allocates the data to be output to the control output 2 termi- nals (terminals 1 and 2.) Communications Variable type Address...
  • Page 163: Auxiliary Output 2 Allocation (Sub2)

    Alarm 2 output 00000009H (9) Alarm 3 output Alarm 3 output 7-5-12 Auxiliary Output 2 Allocation (sub2) Function This parameter allocates the data to be output to the auxiliary output 2 termi- nals (terminals 14 and 15.) Communications Variable type Address Shared...
  • Page 164: Auxiliary Output 4 Allocation (Sub4)

    00000013H (19) Cooling MV transfer output 7-5-14 Auxiliary Output 4 Allocation (sub4) Condition: Analog output models only Function This parameter allocates the data to be output to the auxiliary output 4 termi- nals (terminals 16 and 18.) Communications Variable type Address...
  • Page 165: Transfer Output Upper Limit (Tr1H)/(Tr2H)/(Tr3H)/(Tr4H)

    Condition: The transfer output must be allocated in the control outputs or auxiliary outputs for an analog output model. • This parameter sets the transfer output upper and lower limits used for Function scaling when transfer output is allocated for control and auxiliary output.
  • Page 166: Current Output Type (Ot-1) Voltage Output Type (Ot-2)

    500.0, and the trans- fer output lower limit to 20.0. By setting the SP limit to 0.0 to 100.0 C, the transfer output upper limit will change to 100.0 and the transfer output lower limit will change to 0.0.
  • Page 167: Sensor Error Indicator Used (Sedu)

    • This parameter sets whether the error indicator (ERROR) on the front Function panel of the E5ZN will light or not light when a sensor error is detected. • For the initial setting, when an input channel sensor is not connected dur- ing operation, a sensor error is detected and the ERROR indicator will light.
  • Page 168: Advanced Function Setting Level

    7-6-2 Number of Multi-SP Uses (eU-m) • This parameter sets the multi-SP SPs that are used for the event input. Function • When the number of multi-SP uses setting has been changed, the setting must enabled by executing a software reset or by turning ON the power again.
  • Page 169: Multi-Sp Uses (Mspu)

    Function Set the maximum permissible change width per unit of time (minute) as the “SP ramp set value.” When the “SP ramp set value” is set to 0, the SP ramp function is disabled. • During temperature input, the decimal point position of the SP ramp set value is dependent on the currently selected sensor, and during analog input it is dependent on scaling.
  • Page 170: Standby Sequence Reset Method (Rest)

    “Scaling upper limit” “Scaling lower limit” “Decimal point” (initial setting level) (page 144) 7-6-6 Standby Sequence Reset Method (rest) Condition: The alarm 1 to 3 type must be set to an alarm with a standby sequence. • This parameter sets the conditions for enabling reset after the standby Function sequence of the alarm has been canceled.
  • Page 171: Alarm 3 Open In Alarm (Al3N)

    Close in alarm ON Not lit Open in alarm ON Not lit • Setting changes to “alarm 1 to 3 open in alarm” must be enabled by exe- cuting a software reset or by turning ON the power again. Communications Setting...
  • Page 172: Alarm 1 Hysteresis (Alh1) Alarm 2 Hysteresis (Alh2) Alarm 3 Hysteresis (Alh3)

    • These parameters set the hystereses of alarm outputs 1, 2, and 3. Function • Setting changes to “alarm 1 to 3 hysteresis” must be enabled by execut- ing a software reset or by turning ON the power again. Communications...
  • Page 173: Hba Used (Hbu)

    7-6-10 Heater Burnout Latch (hbl) Condition: Pulse output models only, and the “HBA used” parameter must be set to “ON.” • When this parameter is set to ON, the heater burnout alarm is held until Function either of the following conditions is satisfied: a) Heater burnout detection is set to 0.0 A.
  • Page 174: (Alfa)

    • Normally, use this parameter at its default. Function • This parameter sets the 2-PID constant α. • Setting changes to “α” must be enabled by executing a software reset or by turning ON the power again. Communications Variable type...
  • Page 175: Input Digital Filter (Inf)

    See Also “ PID/OnOff ” (initial setting level) (page 145) 7-6-14 Input Digital Filter (inf) • Sets the time constant of the input digital filter. The following figure shows Function the effect on data after passing through the digital filter:...
  • Page 176: Additional Pv Display (Puad)

    Advanced Function Setting Level Section 7-6 7-6-15 Additional PV Display (pUad) • This parameter enables displaying only the PV. It is added to the top of Function the operation level of the E5ZN-SDL Setting Display Unit. It is used to give the option of displaying the PV and SP, or just the PV only.
  • Page 177: Alarm 1 Latch (A1Lt) Alarm 2 Latch (A2Lt) Alarm 3 Latch (A3Lt)

    Alarm 3 Latch (a3lt) Condition: The alarm type must be set to other than “no alarm.” • When these parameters are set to ON, the latch function is added to the Function alarm functions. This means that once the alarm function has turned ON, the alarm output function is held ON until the power is turned OFF.
  • Page 178: Input Error Output (Sero)

    • When the sensor error alarm output is enabled (on), alarm 1 for ch1 will turn ON when a sensor error occurs in a ch1 input, and alarm 1 for ch2 will turn ON when a sensor error occurs in a ch2 input.
  • Page 179 Advanced Function Setting Level Section 7-6 • Related Parameter See Also “Input type” (initial setting level) (page 143)
  • Page 180: Communications Setting Level

    Setting range Unit Default 00000007H to 00000008H (7 or 8) 7-7-2 Communications Stop Bit (sbit) Setting changes to “communications stop bit” must be enabled by executing a Function software reset or by turning ON the power again. Communications Variable type Address...
  • Page 181: Communications Response Wait Time (Sdwt)

    Communications Setting Level Section 7-7 7-7-4 Communications Response Wait Time (sdwt) Setting changes to “communications response wait time” must be enabled by Function executing a software reset or by turning ON the power again. Communications Variable type Address Shared 0016 or 0116...
  • Page 183: Troubleshooting

    Troubleshooting Procedure ........
  • Page 184: Troubleshooting Procedure

    Troubleshooting Procedure Section 8-1 Troubleshooting Procedure If the E5ZN has an error, refer to the following items to find the possible cause of the error and take corrective measures. 1,2,3... 1. Indicators Check the operating status of the E5ZN using the indicators.
  • Page 185: Communications Errors

    Make sure that different numbers are assigned to once on the same transmission path. all the E5ZNUnits that communicate with the host. Communications data error due to ambient noise. • Move the communications cable away from the source of noise. • Use shielded communication cables.
  • Page 186: Temperature Sensing Errors

    E5ZN. the metal of the thermocouple or that of the com- pensating conductors. A screw of the terminal block of the E5ZN is loos- Tighten the screw. ened and improper contact is resulting. • Use sufficiently thick compensating conduc- Leads or compensating conductors of a thermo- tors.
  • Page 187 1. Connect a 100- Ω resistor between the A and B temperature sensor input 1,2,3... terminals and short-circuit the B terminals. 2. If the temperature sensed by the E5ZN is 0.0 ° C or 32.0 ° F, the E5ZN is op- erating normally. Thermocouple 1,2,3...
  • Page 188: Temperature Control Errors

    E5ZN. Polarity or wiring of a load is incorrect. Correct the wiring of the load. A screw of the terminal block of the E5ZN is loos- Tighten the screw. ened and improper contact is resulting. Power is not supplied to heaters.
  • Page 189 P constant can be allowed. • Execute autotuning. E5ZN has a short integral time or small I constant. • Increase the I constant keeping within the range where the response delay caused by the I constant can be allowed.
  • Page 190: Output Errors

    When designating multi-SP with event input, the Set the E5ZN so that the ON or OFF status of the ON or OFF status of the input is not kept on hold. input is kept on hold while designating the multi- SP with the event input.
  • Page 191: Hb Alarm Errors

    Wire the Current Transformer to the correct chan- nel of the E5ZN. nel. Heaters are controlled directly with an alarm out- Change the wiring so that the CT input is con- put. nected to the correct control output. Settings E5ZN has not started control operation.
  • Page 192: Key Operations Not Functioning

    Remedy Setting Setting change protection Set the setting change protec- (protect level) is set to ON. tion (protect level) to OFF. Cannot Move to Another Level from the Setting Display Device Probable cause Remedy Setting Initial setting/communications Change the setting/communi-...
  • Page 193: Error Displays

    Check the wiring of inputs for mistakes in wiring, disconnections, short-cir- cuits, and the input type. If no abnormality is found in the wiring and input type, turn the power OFF then back ON again. If the display remains the same, the E5ZN must be repaired.
  • Page 194: Current Value Exceeded (Ffff)

    8-8-5 Disabled Status (----) Meaning This error is displayed when one of the following errors has occurred in the connection with the E5ZN. • The connecting cable is disconnected. • The power supply to the E5ZN-SDL has been turned OFF while in copy mode.
  • Page 195: A Specifications

    Heater burnout alarm output turns OFF. 50.0 A: Heater burnout alarm output turns ON. Min. detection ON time (See note.) 190 ms Note When the control output ON time is less than 190 ms, heater burnout detection and heater current measurement are not performed.
  • Page 196 Voltage range: 15 to +10% of rated voltage When 0 to 20 mA DC is selected, the accuracy for 0 to 4 mA is ±0.5% FS + 0.7 mA. When 0 to 5 VDC is selected, the accuracy for 0 to 1 V is ±0.5% FS + 0.175 V.
  • Page 197: Specifications

    1000 VAC (for 1 minute) Vibration resistance 50 Hz 98m/s {10G} Weight Approx. 11.5 g Approx. 50 g Accessory None Armature (2) Plug (2) Note The maximum continuous current of the E5ZN is 50 A. External Dimensions (Unit: mm) E54-CT1 10.5...
  • Page 198 Specifications Appendix A E54-CT3 2.36 dia.
  • Page 199 1,999 to 9,999 or 199.9 to 999.9 • Default is 0. • The applicable standards for each of the above input ranges are as follows: • K, J, T, E, N, R, S, B: JIS C1602-1995, IEC 584-1 •...
  • Page 200 No. 1 display: No. 2 display: Setting (monitor) value Characters Default Displayed when a screen for PV display only has been added in additional PV display (advanced function setting level). PV/SP Temperature: Range specified for sensor input Analog: Scaling lower limit 5% FS to scaling...
  • Page 201 Default Input type Platinum-resistance thermometer input: in-t 0: Pt ( 200 to 850°C or 300 to 1,500°F) 1: Pt ( 199.9 to 500.0°C or 199.9 to 900.0°F) 2: Pt (0.0 to 100°C or 0.0 to 210.0°F) 3: JPt ( 199.9 to 500.0°C or 199.9 to 900.0°F)
  • Page 202 0: Heating control output for ch1 out1 1: Cooling control output for ch1 2: Alarm 1 and HB alarm OR output for ch1 (pulse output models only) Alarm 1 and sensor error alarm OR output for ch1 (analog output models only)
  • Page 203 0: Heating control output for ch1 1: Cooling control output for ch1 2: Alarm 1 and HB alarm OR output for ch1 (pulse output models only) Alarm 1 and sensor error alarm OR output for ch1 (analog output models only)
  • Page 204 (pulse output models only) Heater burnout latch off: Disabled on: Enabled (pulse output models only) Heater burnout hysteresis 0.1 to 50.0 (pulse output models only) alfa 0.65 0.00 to 1.00 MV upper limit Standard control: Operation lower limit +0.1 ol-h 105.0...
  • Page 205 No. 1 display: No. 2 display: Set (monitor) value Characters Default Input error output sero off: Sensor error alarm output disabled on: Sensor error alarm output enabled (analog output models only) Cold junction compensation off: External, on: Internal method Communications Setting Level Parameter No.
  • Page 207: C Ascii Table

    Appendix C ASCII Table Upper Lower SPACE ‘ “ & ‘ < >...
  • Page 209: Index

    2-PID control 2-point temperature input shift 3-position control baud rate – additional PV display additional temperature input shift value display calculating the detection current value address characteristics adjustment level cold junction compensation method advanced function setting level command frame...
  • Page 210 ON/OFF control heating and cooling control one-point shift heating control period open in alarm hysteresis operation after power ON operation after turning ON the power supply operation commands initial setting level operation display initial setting/communications protection operation level input digital filter...
  • Page 211 RUN/STOP upper limit alarm upper limit temperature input shift value upper limit values using the keys scaling scaling lower limit scaling upper limit sensor input setting ranges/control ranges variable area...
  • Page 212 Index write setting data write to multiple variable area write to variable area...
  • Page 213: Revision History

    A manual revision code appears as suffix to catalog number on front cover of manual. Cat. No. H113-E1-03B Revision code The following table outlines changes made to manual during each revision. Page numbers refer to previous version. Revision code Date...
  • Page 214 Revised content September 2002 Pages xi, 14, 42, 46, 72, 80, 81, 85, 86, 90, 91, 104, 105, 138, 153, 162, 189, and 190: Added or revised information for upgraded pulse output models. Page14: Added an alternative model to Recommended power supply.
  • Page 215 Regional Headquarters OMRON EUROPE B.V. Wegalaan 67-69, NL-2132 JD Hoofddorp The Netherlands Tel: (31)2356-81-300/Fax: (31)2356-81-388 OMRON ELECTRONICS LLC 1 East Commerce Drive, Schaumburg, IL 60173 U.S.A. Tel: (1)847-843-7900/Fax: (1)847-843-8568 OMRON ASIA PACIFIC PTE. LTD. 83 Clemenceau Avenue, #11-01, UE Square,...
  • Page 216 Authorized Distributor: Cat. No. H113-E1-03B Note: Specifications subject to change without notice Printed in Japan 1105 (0101)

Table of Contents