Advanced Function Setting Level

7-6-15 Additional PV Display (pUad)

Function
Communications
Settings

7-6-16 Additional Temperature Input Shift Value Display (isdp)

Function
Communications
Settings

7-6-17 Temperature Input Shift Type (istp)

Function
Communications
162
• This parameter enables displaying only the PV. It is added to the top of
the operation level of the E5ZN-SDL Setting Display Unit. It is used to
give the option of displaying the PV and SP, or just the PV only.
• Setting changes to "additional PV display" must be enabled by executing
a software reset or by turning ON the power again.
ch
Shared
C3
Setting range
00000000H to 00000001H
0: Not added (off)
1: Added (on)
• This parameter conceals the display of the temperature input shift value in
the E5ZN-SDL Setting Display Unit operation level. The input shift func-
tion is enabled even when this parameter is set to "no display."
• Setting changes to "temperature input shift value display/not display"
must be enabled by executing a software reset or by turning ON the
power again.
ch
Shared
C3
Setting range
00000000H to 00000001H
0: No display (off)
1: Display (on)
Condition:
Upgraded pulse output models and analog output models only
• This parameter sets whether a one-point shift or a two-point shift is used
as the input shift method.
• This function can be used with upgraded pulse output models and analog
output models only.
ch
Variable type
Shared
C3
Variable type
0029 or 0129
Variable type
002A or 012A
Address
003E or 013E
Section 7-6
Address
Unit
Default
-
0: Not added
Address
Unit
Default
-
0: No display