Initial Setup Examples

6-4
Initial Setup Examples
Typical Usage Example
Typical Example 1
0 (K thermocouple 200 to 1,300 ° C)
Input type:
Control method:
ON/OFF control
Alarm type:
2 (upper limit)
20 ° C
Alarm value 1:
100 ° C
SP:
E5ZN unit number: 3
Channel No.:
1
116
On previous Controllers, the sensor input type, alarm type, and control period
were set on DIP switches. These hardware settings are now set using the
setup menus of the E5ZN-SDL. The Level and Mode Keys are used to switch
between setup menus, and the amount of time that you hold the keys down
determines which setup menu you move to.
Changing parameters
in-t
0
in-h
100
Mode Key
in-l
0
cntl
cntl
pid
pid
Setup procedure
Power ON
Set unit
Set channel No.
Initial setting level
Set input specifications
Set control specifications
Set alarm type
Operation level
Set alarm values
Start operation
: indicates that there are more parameters.
Continue to press the Mode Key until the
desired parameter is reached.
Mode Key
Mode Key
Changing numerals
°c
25
0
Power ON
Operation level
°c
25
0
01
Match UNIT/CH using
the UNIT and CH Keys.
°c
25
0
31
Initial setting level
in-t
Check input
0
type.
3u
Mode Key
Use the Up and
cntl
Down Keys to
onof
select ON/OFF
31
control.
Mode Key
alt1
Check alarm
type.
2
31
Mode Key
Press Level Key for at
least one second.
Operation level
°c
Press Up and
25
Down Keys to
100
31
set the SP to
100 ° C.
Mode Key
Press Up and
°c
al-1
Down Keys to
20
set alarm
31
value to 20 ° C.
Mode Key
r-5
Use the Up and
Down Keys to
run
31
select "RUN."
Mode Key
Start operation
Section 6-4
Use the Up and Down Keys
to change numeric data.
PV/SP
Press Level Key for at
least three seconds.
Control stops.
Input type
0
In ON/
OFF
control
onof
In PID
pid
control
Alarm 1
2
type
PV/SP
100
Alarm
20
value 1
During run
run
stop
During stop