Determining the Error from the Current Situation for Output Errors

8-7
Determining the Error from the Current Situation for
Output Errors
No Control Outputs. No Alarm Outputs.
Connection Measured temperature is wrong.
The load polarity or connected terminals are wrong.
A load exceeding the output rating is connected.
No power supply for the load is connected to the transistor
outputs.
The polarity of the load power supply for transistor outputs is
incorrect.
Setting
Set the Operation After Power ON parameter to Stop.
Control does not start.
The specified channel is incorrect.
The control output assignments are incorrect.
The set point is incorrect.
The specified bank is incorrect.
A bank specification for all channels has been assigned to
an event input, and an unintended bank has been selected.
Alarm mode is set to 0 (no alarm).
Alarm mode is set to an alarm with a standby sequence.
The deviation alarm and absolute-value alarm settings for
alarm mode are incorrect.
224
Possible cause
Countermeasure
• Perform the action outlined in 7.5.
• Rewire correctly.
• Reduce the load to within the rating.
• Get the Unit repaired if it is malfunctioning.
• Use a power supply suitable for the output rating and load.
• Rewire correctly.
• Execute a RUN (start operation) operation command after
the power is turned ON.
• Set the Operation After Power ON parameter to Continue.
• Execute a RUN (start operation) operation command.
• Set the correct channel number.
• Set the correct control output assignments.
• Set the correct set point.
• Set the correct bank.
• Assign the bank of the channel for which the bank is to be
changed to an event input.
• Set the correct alarm mode.
• Set to an alarm without a standby sequence.
• Set the correct alarm mode.