Omron E5ZN Operation Manual page 134

Hide thumbs Also See for E5ZN:
Table of Contents

Advertisement

Using Copy Mode
UNIT
CH
COPY
UNIT
CH
COPY
E5ZN-SDL
UNIT
CH
COPY
UNIT
CH
COPY
120
3. Upload all the parameters from the Master.
In this example, all the parameters from unit number 1 will be uploaded to
the E5ZN-SDL.
Press the Level Key for at least one second to start the upload.
"UP" will flash on the display during the upload. The mode will return auto-
matically to operating mode when the upload has been completed.
4. The unit number of the Unit to which the data is to be downloaded will
change to the uploaded unit number. When uploading has been complet-
ed, turn OFF the power and disconnect the Unit (unit number 1) that has
been uploaded from the socket or change the unit number to avoid using
the same unit number twice during the download.
In this example, change the Master unit number from 1 to 5, and change
the unit number of the Unit to which the data is to be downloaded from
number 2 to number 1. The system configuration will change to the config-
uration shown in the following diagram.
E5ZN E5ZN E5ZN
5
1
3
Master
Copy destination
5. Turn ON the power and press the COPY Key for at least one second to
move to copy mode.
6. Use the Up and Down Keys to select "DOWN" on the No. 2 display. Press
the UNIT Key to select unit number 1 for the download where data is to be
copied to.
(The lowest unit number that is being uploaded will be displayed in the
download unit number display. At initialization, no upload data exists, so
the unit number display is blank.)