Variable Area Map
Variable
Address
ch
type
C3
012F
-
0130
0131
0132
0133
0134
0135
0136
0137
0138
0139
013A
013B
013D
013E
104
Setting data name
Auxiliary output 3 alloca-
tion (See note 2.)
Auxiliary output 4 alloca-
tion (See note 2.)
OUT1 transfer output
upper limit (See note 2.)
OUT1 transfer output
lower limit (See note 2.)
OUT2 transfer output
upper limit (See note 2.)
OUT2 transfer output
lower limit (See note 2.)
SUB3 transfer output
upper limit (See note 2.)
SUB3 transfer output
lower limit (See note 2.)
SUB4 transfer output
upper limit (See note 2.)
SUB4 transfer output
lower limit (See note 2.)
Current output type
(See note 2.)
Voltage output type
(See note 2.)
Sensor error indicator
used
(See note 3.)
Input error output
(See note 3.)
Input shift type
(See note 3.)
00000000H (0):
Heating control output for ch1
00000001H (1):
Cooling control output for heating/cooling con-
trol for ch1
00000002H (2):
Alarm 1 and sensor error alarm OR output for
ch1
00000003H (3):
Alarm 2 output for ch1
00000004H (4):
Alarm 3 output for ch1
00000005H (5):
Heating control output for ch2
00000006H (6):
Cooling control output for heating/cooling con-
trol for ch2
00000007H (7):
Alarm 1 and sensor error alarm OR output for
ch2
00000008H (8):
Alarm 2 output for ch2
00000009H (9):
Alarm 3 output for ch2
0000000AH (10): SP transfer output for ch1
0000000BH (11): Ramp SP transfer output for ch1
0000000CH (12): PV transfer output for ch1
0000000DH (13): Heating MV transfer output for ch1
0000000EH (14): Cooling MV transfer output for ch1
0000000FH (15): SP transfer output for ch2
00000010H (16): Ramp SP transfer output for ch2
00000011H (17): PV transfer output for ch2
00000012H (18): Heating MV transfer output for ch2
00000013H (19): Cooling MV transfer output for ch2
Same as for auxiliary output 3 allocation
FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
FFFFF831H to 0000270FH ( 1,999 to 9,999 or 199.9 to 999.9)
00000000H(0): 4 to 20 mA DC
00000001H(1): 0 to 20 mA DC
00000000H(0): 1 to 5 VDC
00000001H(1): 0 to 5 VDC
00000000H(0): Indicators always not lit.
00000001H(1): Sensor error indicator lit (ch1 only)
00000002H(2): Sensor error indicator lit (ch2 only)
00000003H(3): Sensor error indicator lit (ch1 or ch2)
00000000H(0): OFF
00000001H(1): ON
00000000H(0): One-point temperature input shift
00000001H(1): Two-point temperature input shift
Section 5-10