AR Area
3-6-2

Flags/Bits for Inner Boards (AR 05 and AR 06)

High-speed Counter Board Slot 2 Flags/Bits (AR 05 to AR 06)
Word
Bit(s)
AR 05
00
High-speed Counter 1 Reset Bit
01
High-speed Counter 2 Reset Bit
02
High-speed Counter 3 Reset Bit
03
High-speed Counter 4 Reset Bit
04 to 07
Not used.
08
High-speed Counter 1 Comparison Stop Bit
09
High-speed Counter 2 Comparison Stop Bit
10
High-speed Counter 3 Comparison Stop Bit
11
High-speed Counter 4 Comparison Stop Bit
12
High-speed Counter 1 Stop Bit
13
High-speed Counter 2 Stop Bit
14
High-speed Counter 3 Stop Bit
15
High-speed Counter 4 Stop Bit
AR 06
00
External Output 1 Force-set Bit
01
External Output 2 Force-set Bit
02
External Output 3 Force-set Bit
03
External Output 4 Force-set Bit
04
External Output Force-set Enable Bit
05 to 15
Not used.
Pulse I/O Board Slot 2 Flags/Bits (AR 05 to AR 06)
Word
Bit(s)
AR 05
00 to 07
High-speed Counter 1 Range Comparison Flags
Bit 00 ON: Counter PV satisfies conditions for comparison range 1
Bit 01 ON: Counter PV satisfies conditions for comparison range 2
Bit 02 ON: Counter PV satisfies conditions for comparison range 3
Bit 03 ON: Counter PV satisfies conditions for comparison range 4
Bit 04 ON: Counter PV satisfies conditions for comparison range 5
Bit 05 ON: Counter PV satisfies conditions for comparison range 6
Bit 06 ON: Counter PV satisfies conditions for comparison range 7
Bit 07 ON: Counter PV satisfies conditions for comparison range 8
08
High-speed Counter 1 Comparison Flag
OFF: Stopped
ON: Comparing
09
High-speed Counter 1 Overflow/Underflow Flag
OFF: Normal
ON: Overflow or underflow occurred.
10 to 11
Not used.
12 to 15
Port 1 Pulse Output Flags
Bit 12 ON: Deceleration specified. (OFF: Not specified.)
Bit 13 ON: Number of pulses specified. (OFF: Not specified.)
Bit 14 ON: Pulse output completed. (OFF: Not completed.)
Bit 15 ON: Pulse output in progress. (OFF: No pulse output.)
Function
Operation
Operation
Z Phase and software reset
0: Z-phase reset disabled
1: Z-phase reset enabled
Software reset only
0: Software reset disabled
0→1: Executes software reset
---
0→1: Starts comparison.
1→0: Stops comparison.
0: Continues operation.
1: Stops operation.
0: Not valid
1: Forced ON
0: Force-setting of outputs 1 to 4 disabled
1: Force-setting of outputs 1 to 4 enabled
---
Section 3-6
165