Omron CQM1H - PROGRAM Programming Manual page 557

Programmable controllers; inner boards
Table of Contents

Advertisement

Memory Areas
Word
Bit(s)
SR 254
00
1-minute Clock Pulse (30 seconds ON; 30 seconds OFF)
01
0.02-second Clock Pulse (0.01 second ON; 0.01 second OFF)
02 to 03
Not used.
04
Overflow (OF) Flag
Turns ON when the result of a calculation is above the upper limit of signed binary data.
05
Underflow (UF) Flag
Turns ON when the result of a calculation is below the lower limit of signed binary data.
06
Differential Monitor Complete Flag
Turns ON when differential monitoring is complete.
07
STEP(08) Execution Flag
Turns ON for 1 cycle only at the start of process based on STEP(08).
08
HKY(––) Execution Flag
Turns ON during execution of HKY(––).
09
7SEG(88) Execution Flag
Turns ON during execution of 7SEG(88).
10
DSW(87) Execution Flag
Turns ON during execution of DSW(87).
11 to 12
Not used.
13
Communications Unit Error Flag
Turns ON when an error occurs in a Communications Unit. This flag mirrors the opera-
tion of the Communications Unit Error Flag (AR 0011).
14
Not used.
15
Inner Board Error Flag
Turns ON when an error occurs in an Inner Board mounted in slot 1 or slot 2. The error
code for slot 1 is stored in AR 0400 to AR 0407 and the error code for slot 2 is stored in
AR 0408 to AR 0415.
SR 255
00
0.1-second Clock Pulse (0.05 second ON; 0.05 second OFF)
01
0.2-second Clock Pulse (0.1 second ON; 0.1 second OFF)
02
1.0-second Clock Pulse (0.5 second ON; 0.5 second OFF)
03
Instruction Execution Error (ER) Flag
Turns ON when an error occurs during execution of an instruction.
04
Carry (CY) Flag
Turns ON when there is a carry in the results of an instruction execution.
05
Greater Than (GR) Flag
Turns ON when the result of a comparison operation is "greater."
06
Equals (EQ) Flag
Turns ON when the result of a comparison operation is "equal," or when the result of an
instruction execution is 0.
07
Less Than (LE) Flag
Turns ON when the result of a comparison operation is "less."
Note Writing is not possible for the following words: SR 248 through SR 251, and SR 253 through SR 255.
Explanation of SR Bits
SR 25211 (Forced Status Hold Bit)
When the forced set/reset status is cleared, the bits that were forced will be turned ON or OFF as follows:
Forced set cleared:
Forced reset cleared:
All force-set or force-reset bits will be cleared when the PC is switched to RUN mode unless DM 6601 in the
PC Setup has been set to maintain the previous status of the Forced Status Hold Bit when power is turned on.
This setting can be used to prevent forced status from being cleared even when power is turned on.
Turn this bit ON and OFF from a Programming Device.
532
Bit turned ON
Bit turned OFF
Function
Appendix C
Page
---
---
328
328
147
231
431
424
427
427
---
---
---
---
---
---
---
---
---