Omron CV/CVM1 Replacement Manual

From cv/cvm1 to cs1

Advertisement

Quick Links

CV/CVM1
Replacement Guide
From CV/CVM1 to CS1

Advertisement

Table of Contents
loading

Summary of Contents for Omron CV/CVM1

  • Page 1 CV/CVM1 Replacement Guide From CV/CVM1 to CS1...
  • Page 2 About this document This document provides the reference information for replacing CV/CVM1 PLC systems with CS1 series PLC. This document does not include precautions and reminders ;please read and understand the important precautions and reminders described on the manuals of PLCs (both of PLC used in the existing system and PLC you will use to...
  • Page 3 Related Manuals CPU Units Man.No. Model Manual W341 CQM1H-PRO01 CS/CJ Series Programming Consoles OPERATION MANUAL CQM1-PRO01 C200H-PRO27 CS1W-KS001 W394 CS1G/H-CPU□□H CS/CJ/NSJ Series PROGRAMMING MANUAL CS1G/H-CPU□□-V1 CS1D-CPU□□H CS1D-CPU□□S CJ1H-CPU□□H-R CJ1G/H-CPU□□H CJ1G-CPU□□P CJ1M/G-CPU□□ NSJ□-□□□□(B)-□□□ W474 CS1G/H-CPU□□H CS/CJ/NSJ Series INSTRUCTIONS REFERENCE MANUAL CS1G/H-CPU□□-V1 CS1D-CPU□□H CS1D-CPU□□S CJ1H-CPU□□H-R...
  • Page 4 Special I/O Units Man.No. Model Manual W345 CS1W-AD0□□-V1/-AD161 CS/CJ Series Analog I/O Units OPERATION MANUAL CS1W-DA0□□ CS1W-MAD44 CJ1W-AD0□□-V1/-AD042 CJ1W-DA0□□/-DA042V CJ1W-MAD42 W368 CS1W-PTS□□ CS/CJ Series Analog I/O Units OPERATION MANUAL CS1W-PTW□□ CS1W-PDC□□ CS1W-PTR□□ CS1W-PPS□□ CS1W-PMV□□ CJ1W-PTS□□ CJ1W-PDC□□ CJ1W-PH41U W426 CS1W-NC□71 CS/CJ Series Position Control Units OPERATION MANUAL CJ1W-NC□71(-MA) W435 CS1W-MCH71...
  • Page 5 Man.No. Model Manual W304 C200HW-COM01 C200HW Communication Boards OPERATION MANUAL C200HW-COM02-V1 to C200HW-COM06-EV1 W206 CV500-BSC11/21/31/41/51/61 CVM1/CV Series BASIC Units OPERATION MANUAL W207 CV500-BSC11/21/31/41/51/61 CVM1/CV Series BASIC Units REFERENCE MANUAL W254 CV500-MC221/421 CVM1/CV Series Motion Control Unit OPERATION MANUAL:INTRODUCTION W255 CV500-MC221/421 CVM1/CV Series Motion Control Unit OPERATION MANUAL:DETAILS Network Communications Units Man.No.
  • Page 6 W204 CV500-RM211/221 SYSMAC BUS/2 CV-series Remote I/O SYSTEM MANUAL CV500-RT211/221 W348 DRT1-COM DeviceNet MULTIPLE I/O TERMINAL OPERATION MANUAL W434 CVM1-LK401 CV/CVM1 Series PC Link Unit OPERATION MANUAL W367 CS1W-SLK11/21 SYSMAC LINK Units OPERATION MANUAL Support Software Man.No. Model Manual W463 CXONE-AL□□C-V4...
  • Page 7 WHETHER SUCH CLAIM IS BASED ON CONTRACT, WARRANTY, NEGLIGENCE, OR STRICT LIABILITY. In no event shall the responsibility of OMRON for any act exceed the individual price of the product on which liability is asserted. IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY, REPAIR, OR OTHER CLAIMS...
  • Page 8 Performance data given in this manual is provided as a guide for the user in determining suitability and does not constitute a warranty. It may represent the result of OMRON's test conditions, and the users must correlate it to actual application requirements. Actual performance is subject to the OMRON Warranty and Limitations of Liability.
  • Page 9 Application Considerations SUITABILITY FOR USE OMRON shall not be responsible for conformity with any standards, codes, or regulations that apply to the combination of products in the customer's application or use of the products. At the customer's request, OMRON will provide applicable third party certification documents identifying ratings and limitations of use that apply to the products.
  • Page 10 MEMO...
  • Page 11: Table Of Contents

    From CV/CVM1 to CS1 Table of Contents Work flow................................2 Selecting the model...............................3 Reading data from CV/CVM1 ..........................6 Converting the program for CS ..........................8 Writing data to CS ...............................10 Appendix ................................12 Appendix A: Instruction conversion by the Change Model function of CX-Programmer ........12 Appendix B: Difference in data area allocation.......................14...
  • Page 12: Work Flow

    Work flow This section describes the flow of work you have to follow when you replace CV/CVM1 CPU Units with CS-series CPU Units. Read the reference pages for details. 1) Preliminary Steps: Take the following steps before starting the replacement work.
  • Page 13: Selecting The Model

    The table below lists the models of CV/CVM1 series Units and corresponding models of CS-series Units. Select a CS series model which is compatible with or one with similar specification to the CV/CVM1 series model you use. Refer to the following manual for details of each model.
  • Page 14 Expansion Backplanes CV500-CN311 (30 cm) Cables > With CV/CVM1, you have to connect two cables between a CPU Unit and an Expansion Rack: one CV500-CN611 (60 cm) CS1W-CN313 (30 cm) is this connecting cable and the other is an I/O Cable.
  • Page 15 Support software CV Support Software CX-Programmer Ver.3.0 or Only CX-Programmer can be used with CS-series CPU Units. SYSMAC Support Software higher CX-Programmer is included in Omron CX-One FA integrated Tool Package. CX-Programmer Factory intelligent FIT10 None Use commercially available personal computers.
  • Page 16: Reading Data From Cv/Cvm1

    CS1W-CIF31 Peripheral port (1) Mount the peripheral interface (CV500-CIF01) to the CV/CVM1 CPU unit, and connect it with the personal computer. (2) Start up the CX-Programmer. (From the Windows Start menu, select All Programs - OMRON - CX-One - CX-Programmer - CX-Programmer.)
  • Page 17 Load ladder programs, PLC setting and I/O table from the CV/CVM1. (Select PLC – Transfer – From PLC to PC.) Click the OK Button to read them. (6) Load the PLC memory data (Data Memory). (Select PLC - Edit - Memory.) Scroll and check all the areas.
  • Page 18: Converting The Program For Cs

    (1) Start the CX-Programmer, and open the program file for CV/CVM1. (Select File – Open.) (2) Change the Device Type from CV/CVM1 to CS1 (Select PLC - Change Model to show the below dialog box.) * Keep the data loaded from CV/CVM1 when you change the model to convert the program. The only data that can be converted is ladder program.
  • Page 19 (5) CV/CVM1 and CS-series are different in the word allocation. Refer to Appendix B. Difference in data area allocation, and modify the ladder program. (6) CV/CVM1 and CS-series are different in a part of PLC setting. Refer to Appendix C. Change in PLC settings, and change the PLC settings.
  • Page 20: Writing Data To Cs

    Writing data to CS Transfer the converted and modified programs, PLC settings and data memory to CS-series CPU Unit. Required items Support software CX-One (PC) CXONE-AL[][]C-V[]/ AL[][]D-V[] (CX-Programmer) Connecting cable CS1W-CN226/626 + CS1W-CIF31 CX-Programmer Connecting cable CS1W-CN226/626 CS1W-CIF31 CS1D Peripheral port (1) Connect the CS1 CPU Unit and the PC.
  • Page 21 (5) Transfer the PLC memory (Select D (Data Memory)). (Select PLC - Edit – Memory.) (6) Make the CX-Programmer offline.
  • Page 22: Appendix

    STEP(8) STEP(8) The operand data must be set by Work Area (WR) or Index Resistors (indirect). Same as CV/CVM1 Change the operand. SNXT(9) SNXT(9) The operand data must be set by Work Area (WR) or Index Resistors (indirect).
  • Page 23 The data type of the 2nd operand is changed from BCD to BIN. For a constant, the # mark is Same as CV/CVM1 converted to & mark. To use word data, change the data type of word from BCD to BIN.
  • Page 24: Appendix B: Difference In Data Area Allocation

    Appendix B: Difference in data area allocation This table outlines the difference in the data allocation between CV/CVM1 and CS. Refer to the related manuals for details. Item CV/CVM1-series CS-series Remark I/O allocation "Free location and free words "Free location and free words...
  • Page 25: Appendix C: Difference In The Plc Setting Methods

    Appendix C: Difference in the PLC setting methods This section explains the difference of PLC settings on CV/CVM1 and CS-series CPU Units. The figure below shows the 1) setting tab on the PLC Settings window, 2) Group of settings in the tab, and 3) Setting items in each group.
  • Page 26 Execution Conttols 1 Execution Setting CPU Bus Units are initializing. There is no - Run program when Bus Units - Start tunning program when functional difference between CV/CVM1 and initialize initializing Unit/Inner board recognition Execution controls None Specifies whether to handle the power off Execution Conttols 1 interruption as not fatal error or not.
  • Page 27 Specifies the cycle time. The cyle time is set - Cycle Time - Constant Cycle Time to the set time. There is no functional difference between the CV/CVM1 and CS. Timings Timings Set the interval of scheduled interrupt. - Scheduled Interrupt Interval...
  • Page 28: Appendix D: Corresponding Input/Output Units

    (4) If the internal current consumption is different, check if enough power supply capacity is provided. (5) Detaied specifications are different. Refer to the related manuals for the detailed specifications. DC Input Units CV/CVM1-series Unit Corresponding CS-series Unit Model: C500-ID112...
  • Page 29 (6) If the voltage and current consumption of external power supply is different, check if enough power supply capacity is provided. (7) Detailed specifications are different. Refer to the related manuals for the detailed specifications. Relay Output Units CV/CVM1 Unit Corresponding CS-series Unit Model: C500-OC221 Model: CS1W-OC211...
  • Page 30 Triac Output Units CV/CVM1 Unit Corresponding CS-series Unit Model: C500-OA121 Model: CS1W-OA211 Specification: 132 VAC, 1 A Specification: 250 VAC, 0.5 A Terminal block, 16 points Terminal block, 16 points Model: C500-OA222 Model: CS1W-OA211 Specification: 250 VAC, 1 A Specification: 250 VAC, 0.5 A...
  • Page 31 (5) If the voltage and current consumption of external power supply is different, check if enough power supply capacity is provided. (6) Functionally they are supported. Refer to the related manuals for the detailed specifications. DC Input/Transistor Output Unit CV/CVM1 Unit Corresponding CS-series Unit Model: C500-MD211CN Model: CS1W-MD261...
  • Page 32 2011 P076-E1-01 0911(-)