Special Math Instructions
Example
00001
5-23-5 ARITHMETIC PROCESS – APR(––)
Limitations
Description
Flags
344
In the following example, the BCD contents of the 8 words from DM 0000 to
DM 0007 are added when IR 00001 is ON and the result is written to DM
0010 and DM 0011.
@SUM(−−)
#0008
DM 0000
DM 0010
DM 0000 0001
DM 0001 0002
DM 0002 0003
DM 0003 0004
DM 0004 0005
DM 0005 0006
DM 0006 0007
DM 0007 0008
Ladder Symbols
APR(−− )
@APR(−− )
C
S
D
For trigonometric functions S must be BCD from 0000 to 0900 (0 °≤ θ ≤ 90 ° ).
DM 6144 to DM 6655 cannot be used for D.
When the execution condition is OFF, APR(––) is not executed. When the exe-
cution condition is ON, the operation of APR(––) depends on the control word
C.
If C is #0000 or #0001, APR(––) computes sin( θ ) or cos( θ )*. The BCD value of
S specifies θ in tenths of degrees.
If C is an address, APR(––) computes f(x) of the function entered in advance
beginning at word C. The function is a series of line segments (which can
approximate a curve) determined by the operator. The BCD or hexadecimal
value of S specifies x.
ER:
Indirectly addressed EM/DM word is non-existent.
(Content of *EM/*DM word is not BCD, or the EM/DM area boundary
has been exceeded.)
For trigonometric functions, x > 0900. (x is the content of S.)
A constant other than #0000 or #0001 was designated for C.
The linear approximation data is not readable.
EQ:
The result is 0000.
Address Instruction
00000
LD
00001
@SUM(−−)
Operand Data Areas
IR, SR, AR, DM, EM, HR, TIM/CNT, LR, #
C
S: Input data source word
S
IR, SR, AR, DM, EM, HR, TIM/CNT, LR
D
D: Result destination word
IR, SR, AR, DM, EM, HR,TIM/CNT, LR
Section 5-23
Operands
00001
#
0008
DM
0000
DM
0010
DM 0010 0036
DM 0011 0000
C: Contr ol w ord