Multi-Function Analog Output And Pulse Monitor Output; Setting The Multi-Function Analog Output (N065 Through N067) - Omron SYSDRIVE 3G3MV SERIES User Manual

Sysdrive 3g3mv series multi-function compact inverter
Hide thumbs Also See for SYSDRIVE 3G3MV SERIES:
Table of Contents

Advertisement

Basic Operation

5-11 Multi-function Analog Output and Pulse Monitor Output

The 3G3MV Inverter incorporates multi-function analog output terminals (AM and AC).
A parameter setting makes it possible to output pulse monitor signals from these termi-
nals. Make the necessary settings in these terminals according to the application.
5-11-1 Setting the Multi-function Analog Output (n065 through
n067)
• By setting n065 for multi-function analog output type selection to 0 for analog voltage output, analog
monitoring is possible through the multi-function analog output terminals.
• A monitoring item is set in n066 (multi-function analog output selection). Six items including the output
frequency and current are available.
• Set the analog output characteristics in n067 (multi-function analog output gain).
n065
Multi-function Analog Output Type
Selection
Setting
0, 1
range
Set Values
Value
0
Analog voltage output (with monitoring item set in n066)
1
Pulse train output (according to output frequency set in n150)
n066
Multi-function Analog Output
Setting
0 to 5
range
Set Values
Value
0
Output frequency (Reference: 10-V output at max. frequency)
1
Output current (Reference: 10-V output at rated output current)
2
Main circuit DC voltage (Reference: 10-V output at 400 V DC for 200-V models and 800 V
DC for 400-V models)
3
Vector operation torque monitor (Reference: 10-V output at rated motor torque)
4
Output power (Reference: 10-V output at power equivalent to max. applicable motor capacity
and 0-V output during regenerative operation).
5
Output voltage (Reference: 10-V output at 200 V AC for 200-V models and 400 V AC for
400-V models)
Note Output power cannot be monitored in vector control mode.
n067
Multi-function Analog Output Gain Register
Setting
0.00 to 2.00
range
5-38
Register
0141 Hex
Unit of
1
setting
Description
Register
0142 Hex
Unit of
1
setting
Description
0143 Hex
Unit of
0.01
setting
Chapter 5
Changes during
No
operation
Default setting
0
Changes during
No
operation
Default setting
0
Changes during
Yes
operation
Default setting
1.00